Lenovo Flex System x220 Installation And Service Manual page 336

Compute node
Hide thumbs Also See for Flex System x220:
Table of Contents

Advertisement

80070301-3101ffff : Sensor PCIE 1 Overtemp has transitioned to non-recoverable from a less
severe state.
Sensor PCIE 1 Overtemp has transitioned to critical from a less severe state. The compute node has
attempted a soft shutdown.
May also be shown as 800703013101ffff or 0x800703013101ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
Complete the following steps until the problem is solved: 1. Check the Chassis Management Module
or Flex System Manager event log for any fan- or cooling-related issues. 2. Make sure that the
airflow at the front and rear of the chassis is not obstructed and that fillers are in place and correctly
installed. 3. Make sure that the room temperature is within operating specifications. 4. If there are no
other thermal issues, replace the PCIe Card.
80070301-3102ffff : Sensor PCIE 2 Overtemp has transitioned to non-recoverable from a less
severe state.
Sensor PCIE 2 Overtemp has transitioned to critical from a less severe state. The compute node has
attempted a soft shutdown.
May also be shown as 800703013102ffff or 0x800703013102ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
328
Flex System x220 Compute Node Installation and Service Guide