Power-limited Wiring Requirements

2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-lim-
ited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is illus-
trated below.
AC Power
earth
ground
Figure 2.11 Typical UL Power-limited Wiring Requirements
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Power-limited Circuits
(Class 2)
CAC-5X
Power-limited Circuits (Class 2)
CAC-5X
J13
MS-10UD FACP
Installation
Power-limited
Circuits
(Class 2)
4XTMF
Nonpower-
limited
Circuit
Nonpower-
limited
Circuit
Power-limited
Circuit
(Class 2)