3.7 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit
wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram for the
AUDIO•COMMAND•CENTER•25/50 with two speaker circuits is shown below.
Figure 3.16 Typical Wiring Diagram for UL Power-limited Requirements
Nonpower-limited Circuit
AC Power
Nonpower-limited
56
Power-limited Circuit
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
UL Power-limited Wiring Requirements
Nonpower-limited Circuit