Prack Pr300 S, M, D, L Board Dimensions - Carel PRK300L3FK User Manual

Prack pr300 no power & signal cables together read carefully in the text! compressor rack controller
Table of Contents

Advertisement

ENG
Version
Connector
Signal
J20-6
BC10
J20-7
ID17
J20-8
ID18
J20-9
IDC17
J21-1
NO14
J21-2
C14
J21-3
NC14/---
J21-4
NO15
J21-5
C15
L
J21-6
NC15/---
J22-1
C16
J22-2
NO16
J22-3
NO17
J22-4
NO18
J22-5
C16
J23-1
E-
J23-2
E+
J23-3
GND
J23-1
E-
L
J23-2
E+
J23-3
GND
J24-1
+V term
J24-2
GND
J24-3
+5 Vref
J25-1
E-
S, M, L, D
J25-2
E+
J25-3
GND
J26-1
E-
J26-2
E+
J26-3
GND
J27-1
1
J27-2
2
J27-3
3
J27-4
4
J28-1
1
J28-2
2
J28-3
3
J28-4
4
J29-1
GND
J29-2
VREF
D
J29-3
S1
J29-4
S2
J29-5
S3
J29-6
S4
J29-7
DI1
J29-8
DI2
J30-1
VBAT
J30-2
G0
J30-3
G
(*) depending on model

2.3 pRack pR300 S, M, D, L board dimensions

A
B
B - with USB port and/or built-in terminal
B - with Ultracap module
pRack +0300025EN rel. 1.3 - 17.12.2015
Description
common for analogue input 10
digital input no. 17, 24 Vac/Vdc
digital input no. 18, 24 Vac/Vdc
common for digital inputs 17 and 18 (negative pole for DC power supply)
normally open contact, Relais no. 14/ normally open contact, Relais no. 14 SSR 24 Vac/Vdc (*)
common for Relais no. 14
normally closed contact Relais no. 14/ not used (*)
normally open contact, Relais no. 15/ normally open contact, Relais no. 15 SSR 24 Vac/Vdc (*)
common for Relais no. 15
normally closed contact Relais no. 15/ not used (*)
common for Relais: no. 16, 17, 18
normally open contact, Relais no. 16
normally open contact, Relais no. 17
normally open contact, Relais no.18
common for Relais: no. 16, 17, 18
E- terminal for RS485 connection to the I/O expansion modules (not used)
E+ terminal for RS485 connection to the I/O expansion modules (not used)
GND terminal for RS485 connection to the I/O expansion modules (not used)
E- terminal for RS485 connection to the I/O expansion modules (not used)
E+ terminal for RS485 connection to the I/O expansion modules (not used)
GND terminal for RS485 connection to the I/O expansion modules (not used)
additional power supply terminal Aria (not used)
power supply common
power supply for 0/5 V ratiometric probes
E- terminal for RS485, BMS2 connection
E+ terminal for RS485, BMS2 connection
GND terminal for RS485, BMS2 connection
E- terminal for RS485, FIELDBUS 2 connection
E+ terminal for RS485, FIELDBUS 2 connection
GND terminal for RS485, FIELDBUS 2 connection
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
ExV connection, stepper motor power supply
Earth for the signals
Active probe power supply
Probe 1 (pressure) or external signal 4...20mA
Probe 2 (temperature) or external signal 0...10V
Probe 3 (pressure) or external signal 4...20mA
Probe 4 (temperature)
Digital input 1
Digital input 2
Emergency power supply
Electrical power supply
Electrical power supply
pR300
A
Small
Medium
Buit-in driver
227,5
315
315
60
60
60
70
70
70
-
-
75
Fig. 2.e
Large
315
60
70
-
Tab. 2.n
16
44
B
Tab. 2.m

Hide quick links:

Advertisement

Table of Contents
loading