Carel PRK300L3FK User Manual page 67

Prack pr300 no power & signal cables together read carefully in the text! compressor rack controller
Table of Contents

Advertisement

Mask index
Display description
DO
Status (display only)
Egaa02
Logic
Function (display only)
Device present
Deactivation when fan-
Egab01
spower falls under
Before the activation fans
Egab02
at max for
Ext.Temp.Thr.
Sanitary proc.
start at
Egab03
Duration
Ext.temp.thr
ChillBooster requires
Egab04
maintenance after
Reset maintenance time
Avoid simultaneous
Ehb01
pulses betw.lines
Delay
Force off L2 Comp.s for
line 1 fault
Ehb03
Delay
Switch on L1 Comp.s for
L2 activation
Ehb04
Switch on period
Force off line 2 if line 1
is off
Enable min threshold for
Ehb05
L1 activation
Threshold
Setpoint SH
LowSH thres.
Eia02
LOP thresh.
MOP thresh.
Setpoint SH
LowSH thres.
Eia04
LOP thresh.
MOP thresh.
Enable manual
Eib02
Valve position
Manual valve position:
Enable manual
Eib04
Valve position
Manual valve position:
S1 off set
S1 probe (display)
Eic02
S2 off set
S2 probe (display)
S3 off set
S3 probe (display)
Eic03
S4 off set
S4 probe (display)
Alarm:
EN.
Type:
Eic04
Min.:
Max.:
Alarm min.:
Alarm max.:
Alarm:
EN.
Eic05
Type:
Alarm min.:
Alarm max.:
Alarm:
EN.
Type:
Eic06
Min.:
Max.:
Alarm min.:
Alarm max.:
Alarm:
EN.
Eic07
Type:
Alarm min.:
Alarm max.:
Description
ChillBooster DO position (line 1)
Status of ChillBooster DO (line 1)
Logic of ChillBooster DO (line 1)
Status of ChillBooster function (line 1)
Enable ChillBooster function (line 1)
Fan capacity under which ChillBooster is deactivated (line 1)
Fans work at maximum capacity at least for this time before
ChillBooster activation (line 1)
Outside temperature threshold for ChillBooster activation (line 1)
Enable hygiene procedure (line 1)
Hygiene procedure starting time (line 1)
Hygiene procedure duration (line 1)
Outside temperature threshold for hygiene procedure activati. (line 1)
ChillBooster maximum running time (line 1)
ChillBooster maintenance time reset (line 1)
Enable simultaneous compressor start up inhibition
Delay between start up for compressors on diff erent lines
Enable line 2 compressor switch OFF due to line 1 compressor fault
Delay for line 2 compressor switch off after serious alarm on line 1
compressors
Enable line 1 compressor switch ON due to line 2 compressor
switch ON
Delay for line1 compressor switch on for line 2 compressor switch on
Enable line 2 compressor switch OFF due to line 1 switch OFF
Enable L1 activation by DSS only when suction pressure is greater than
a minimum threshold
Minimum threshold for line 1 activation by DSS
PID control set point (valve 1)
Low superheat protection threshold (valve 1)
Low operating pressure protection threshold (valve 1)
Maximum operating pressure protection threshold (valve 1)
PID control set point (valve 2)
Low superheat protection threshold (valve 2)
Low operating pressure protection threshold (valve 2)
Maximum operating pressure protection threshold (valve 2)
Enable manual positioning (valve 1)
Manual position (valve 1)
Enable manual positioning (valve 2)
Manual position (valve 2)
Probe S1 reading off set (valve 1)
Value read by probe S1 (valve 1)
Probe S2 reading off set (valve 1)
Value read by probe S2 (valve 1)
Probe S3 reading off set (valve 1)
Value read by probe S3 (valve 1)
Probe S4 reading off set (valve 1)
Value read by probe S4 (valve 1)
Abilita l'allarme sonda S1 ( valvola 1 )
Type of probe S1 (valve 1)
Minimum probe S1 reading (valve 1)
Maximum probe S1 reading (valve 1)
Minimum probe S1 alarm threshold (valve 1)
Maximum probe S1 alarm threshold (valve 1)
Enable probe S2 alarm (valve 1 )
Type of probe S2 (valve 1)
Minimum probe S2 alarm threshold (valve 1)
Maximum probe S2 alarm threshold (valve 1)
Enable probe S3 alarm (valve 1)
Type of probe S3 (valve 1)
Minimum probe S3 reading (valve 1)
Maximum probe S3 reading (valve 1)
Minimum probe S3 alarm threshold (valve 1)
Maximum probe S3 alarm threshold (valve 1)
Enable probe S4 alarm (valve 1)
Type of probe S4 (valve 1)
Minimum probe S4 alarm threshold (valve 1)
Maximum probe S4 alarm threshold (valve 1)
Default
...
---
NO
---
NO
95
5
30.0 °C
Disab.
00:00
0
5,0 °C
200
NO
NO
0
NO
0
NO
30
NO
NO
---
11.0
5.0
-50.0
50.0
11.0
5.0
-50.0
50.0
NO
0
NO
0
0.0
---
0.0
---
0.0
---
0.0
---
EN./DIS.
4-20mA
-1.0
9.3
-1.0
9.3
EN./DIS.
CAREL NTC
-50.0
105.0
EN./DIS.
4-20mA
-1.0
30.0
-1.0
30.0
EN./DIS.
CAREL NTC
-50.0
105.0
67
ENG
UOM
Values
---
---, 01...29 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
---
NO / YES
%
0...100
min
0 to 300
...
... (**)
---
DISABLE / ENABLE
---
...
min
0 to 30
...
... (**)
h
0...999
---
NO / YES
---
NO / YES
s
0...999
---
NO / YES
s
0...999
---
NO / YES
s
0...999
---
NO / YES
---
NO / YES
...
... (**)
K
-40.0...180.0
K
-40.0...180.0
---
-60.0... 200.0
---
-60.0... 200.0
K
-40.0...180.0
K
-40.0...180.0
---
-60.0... 200.0
---
-60.0... 200.0
NO/YES
---
Min / Max
NO/YES
---
Min / Max
Barg/psig
Barg/psig
°C/°F
°C/°F
Barg/psig
Barg/psig
°C/°F
°C/°F
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
CAREL NTC / 0-10V EXT. SI-
GNAL / NTC SPKP**T0 / CAREL
NTC-HT
°C/°F
-60.0...200.0
°C/°F
-60.0...200.0
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
Barg/pisg -20.0...200.0
CAREL NTC / NTC SPKP**T0 /
CAREL NTC-HT
°C/°F
-60.0...200.0
°C/°F
-60.0...200.0
pRack +0300025EN rel. 1.3 - 17.12.2015