Carel PRK300L3FK User Manual page 64

Prack pr300 no power & signal cables together read carefully in the text! compressor rack controller
Table of Contents

Advertisement

ENG
Mask index
Display description
Regulation by
Regulation type
Dbb01
...
...
Enable condensing
Dbd01
setpoint compensation
...
...
Cond.temperature/pres-
Dbe01
sure high alarm
Threshold
...
...
Dbf01
Number of present fans
...
...
Modulate speed device
Dbg01
Type (****)
...
...
Mask index
Display description
E.Other funct. (The I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions available
see Appendix A.5)
---
---
Eaaa04
--- (display only)
Upper value
Lower value
Calibration
...
...
DO
Status (display only)
Eaaa45
Logic
Function (display only)
Common oil cooler
Oil pumps number
Eaab04
Enable Aout pump
Setpoint
Eaab05
Diff erential
Eaab06
Pump start delay
Oil pumps number
Eaab07
Enable Aout pump
Setpoint
Eaab08
Diff erential
Threshold
Eaab09
Diff erential
Delay
En.oil lev.manag.
Eaab10
Num.Alarm oil level
Time open
Eaab11
Time close
DO
Status (display only)
Ebaa01
Logic
Function (display only)
Subcooling control
---
Ebab01
Threshold
Subcool.value
(display only)
---
---
Ecaa01
--- (display only)
Upper value
Lower value
Calibration
...
...
DO
Status (display only)
Ecaa12
Logic
Function (display only)
Economizer
Compr.Power Thr.
Ecab04 (*)
Press.Lim.
Disch.T.Thr.
pRack +0300025EN rel. 1.3 - 17.12.2015
Description
Condenser control by temperature or pressure (line 2)
Condenser control type (line 2)
...
Enable setpoint compensation (condenser line 2)
...
Type of high condensing pressure/temperature alarm threshold
(line 2)
High condensing pressure/temperature alarm threshold (line 2)
...
Number of fans (line 2)
...
Fan driver type (line 2)
Type of output, PWM / phase control for condenser modulating device
(line 2)
...
Description
Oil temperature probe position (line1)
Oil temperature probe type (line 1)
Oil temperature probe value (line 1)
Oil temperature probe max. limit (line 1)
Oil temperature probe min. limit (line 1)
Oil temperature probe adjustment (line 1)
...
Oil level valve DO position, compressor 6 (line 1)
Oil level valve DO status, compressor 6 (line 1)
Oil level valve DO logic, compressor 6 (line 1)
Oil level function status, compressor 6 (line 1)
Enable common oil cooling (line 1)
Number of oil pumps for common oil cooler (line 1)
Enable AO of common oil cooler pump (line 1)
Common oil cooler setpoint (line 1)
Common oil cooler diff erential (line 1)
Time delay before the start-up of pump 2 after pump1 turns on (line 1) 0
Screw compressors: number of oil cooler pumps enabled (line1)
Screw compressors: enable AO for oil cooler pump (line 1)
Screw compressors: oil temperature setpoint (line 1)
Screw compressors: oil temperature diff erential (line 1)
Common oil high temperature alarm threshold (line 1)
Common oil high temperature alarm diff erential (line 1)
Common oil high temperature alarm delay (line 1)
Enable oil level management (line 1)
Number of compressor alarm associated with oil level (line 1)
Oil level valve opening time (line 1)
Oil level valve closing time (line 1)
Subcooling valve DO position (line 1)
Status of subcooling valve DO (line 1)
Logic of subcooling valve (line 1)
Subcooling valve function status (line 1)
Enable subcooling function (line 1)
Subcooling control type (line 1)
Threshold for subcooling control (line 1)
Subcooling value (line 1)
Discharge temperature probe position, compressor 1 (line 1)
Type of discharge temperature probe, compressor 1 (line 1)
Discharge temperature value, compressor 1 (line 1)
Maximum discharge temperature value, compressor 1 (line 1)
Minimum discharge temperature value, compressor 1 (line 1)
Discharge temperature probe calibration, compressor 1 (line 1)
...
Economizer valve DO position, compressor 6 (line 1)
Economizer valve DO status, compressor 6 (line 1)
Economizer valve DO logic, compressor 6 (line 1)
Economizer valve function status, compressor 6 (line 1)
Enable economizer function (line 1)
Capacity percentage threshold for economizer activation (line 1)
Condensing temperature threshold for economizer activation (line 1)
Discharge temperature threshold for economizer activation (line 1)
Default
PRESSURE
NEUTRAL
ZONE
...
NO
...
ABSOLUTE
24,0 barg
...
3
...
NONE
----
...
Default
B1
4-20mA
---
30.0 barg
0.0 barg
0.0 barg
...
03
---
NC
---
YES
0
YES
0.0 °C
0.0 °C
0
YES
0.0
0.0
100.0 °C
10.0 °C
0
NO
0
0
0
...
---
NO
---
NO
BY COND. &
LIQUID TEMP.
0.0 °C
0.0 °C
B1
4-20mA
---
30.0 barg
0.0 barg
0.0 barg
...
...
---
NO
---
NO
0
0.0 °C
0.0 °C
64
UOM
Values
---
PRESSURE TEMPERATURE
---
PROPORTIONAL BAND
NEUTRAL ZONE
...
...
---
NO
YES
...
...
---
ABSOLUTE
RELATIVE
...
... (**)
...
...
---
0 to 16
...
...
---
NONE
INVETER
PHASE CONTROL
----
---
MCHRTF*
FCS3*-CONV010
...
...
UOM
Values
---
---, B1...B10 (****)
---
---
NTC - PT1000 - 0-1V - 0-10V -
4-20mA - 0-5V - HTNTC
...
... (**)
...
... (**)
...
... (**)
...
... (**)
...
...
---
---, 01...29 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
---
NO / YES
---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
---
NO (Digital outputs)
YES (Analog output)
...
... (**)
...
-9.9...9.9
s
0...999
---
0 to 1 (Analog output)
0 to 2 (Digital outputs)
---
NO (Digital outputs)
YES (Analog output)
°C/°F
...
°C/°F
...
°C/°F
...
°C/°F
...
s
0 to 32767
---
NO / YES
---
0 to 4/7 (*)
s
0...999
s
0...999
---
---, 01...29 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
---
NO / YES
---
BY COND.& LIQUID TEMP.
ONLY BY LIQUID. TEMP.
...
-9999.9...9999.9
...
-999.9...999.9
---
---, B1...B10 (****)
---
---
NTC - PT1000 - 0-1V - 0-10V-
4-20mA - 0-5V - HTNTC
...
... (**)
...
... (**)
...
... (**)
...
... (**)
...
...
---
---, 01...29 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
---
NO / YES
%
0...100
...
-999.9...999.9
...
-999.9...999.9