Carel PRK300L3FK User Manual page 66

Prack pr300 no power & signal cables together read carefully in the text! compressor rack controller
Table of Contents

Advertisement

ENG
Mask index
Display description
High alarm
High alarm
Delay time
Alarm type
Efa09
Low alarm
Low alarm
Delay time
Alarm type
...
...
Gen.Modulat.1
Efb05
Gen.Modulat.2
Regulation variable
Efb06
Mode
Enable
Efb07
Description
---------------
Setpoint
Efb08
Diff erential
High alarm
High alarm
Efb09
Delay time
Alarm type
Out upper limit
Out lower limit
Efb010
Enable cutoff
Cutoff diff .
Cutoff hys.
Low alarm
Low alarm
Efb20
Delay time
Alarm type
...
...
Gen.alarm 1
Efc05
Gen.alarm 2
Regulation variable
Enable
Efc06
Description
---------------
Alarm type
Efc07
Delay time
...
...
Generic Function Sche-
duler
Efd05
Gen.funct.scheduling
connected to global
scheduling
Efd06
Enable
Activ.Time Bands
TB1: --:-- -> --:--
...
TB4: --:-- -> --:--
Efd07
Changes
Copy to
Gen.A Measure
Efe05
...
---
---
--- (display only)
Efe06/Efe07 (**)
Upper value
Lower value
Calibration
...
...
DI
Status (display only)
Efe16
Logic
Function (display only)
...
...
DO
Status (display only)
Efe21
Logic
Function (display only)
...
...
Modulating.1
Efe29
Type (****)
Status (display only)
...
...
DI
Status (display only)
Egaa01
Logic
Function (display only)
pRack +0300025EN rel. 1.3 - 17.12.2015
Description
High alarm enabling for generic stage function 1
High alarm threshold for generic stage function 1
High alarm delay for generic stage function 1
Low alarm enabling for generic stage function 1
Low alarm threshold for generic stage function 1
Low alarm delay for generic stage function 1
Low alarm delay for generic stage function 1
Type of low alarm for generic stage function 1
...
Enable generic modulating function 1 management
Enable generic modulating function 2 management
Control variable for generic modulating function 1
Direct or reverse modulation
Enabling variable for generic modulating function 1
Enable description change
Description
Setpoint for generic modulating function 1
Diff erential for generic modulating function 1
High alarm enabling for generic modulating function 1
High alarm threshold for generic modulating function 1
High alarm delay for generic modulating function 1
Low alarm enabling for generic modulating function 1
Output upper limit for generic modulating function 1
Output lower limit for generic modulating function 1
Enable cut off function for generic modulating function 1
Cut off diff erential for generic modulating function 1
Cut off hysteresis for generic modulating function 1
Low alarm enabling for generic modulating function 1
Low alarm threshold for generic modulating function 1
Low alarm delay for generic modulating function 1
Low alarm type for generic modulating function 1
...
Enable generic alarm function 1 management
Enable generic alarm function 2 management
Monitored variable for generic alarm function 1
Enabling variable for generic alarm function 1
Enable description change
Description
Alarm type for generic alarm function 1
Delay for generic alarm function 1
...
Enable generic scheduler function
Generic scheduler function considers the same special days and periods
of global scheduler
Enabling variable for generic scheduler function
Day of the week
Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
...
Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
Time band changes action
Copy settings to other days
Generic analogue input A unit of measure selection
...
Generic probe A position
Generic probe A type
Generic probe A value
Generic probe A max. limit
Generic probe A min. limit
Generic probe A adjustment
...
Generic digital input F DI position
Status of generic digital input F DI
Logic of generic digital input F DI
Status of generic digital input F DI
...
Generic stage 1 DO position
Status of generic stage 1 DO
Logic of generic stage 1 DO
Generic stage 1 DO function status
...
Generic modulating 1 AO position
Type of output, PWM / phase control for generic modulating function
1 AO (line 1)
Generic modulating 1 output value
...
ChillBooster fault DI position (line 1)
Status of ChillBooster fault DI (line 1)
Logic of ChillBooster fault DI (line 1)
Status of ChillBooster fault (line 1)
Default
DISAB.
0.0 °C
0
LIGHT
DISAB.
0.0 °C
0
LIGHT
...
DISAB.
DISAB.
---
DIRECT
---
SKIP
---
0.0 °C
0.0 °C
DISAB.
0.0 °C
0
LIGHT
100.0
0.0
NO
0.0 °C
0.0 °C
DISAB.
0.0 °C
0
LIGHT
...
DISAB.
DISAB.
---
---
SKIP
---
LIGHT
0
...
DISAB.
NO
---
---
---
...
---
---
0
°C
...
B1
4-20mA
---
30.0 barg
0.0 barg
0.0 barg
...
---
---
NC
---
...
...
---
NO
---
...
0
FCS1*-CON-
VONOFF
0
...
---
---
NC
---
66
UOM
Values
---
DISABLE / ENABLE
...
... (**)
s
0...9999
---
LIGHT / SERIOUS
---
DISABLE / ENABLE
...
... (**)
s
0...9999
---
LIGHT / SERIOUS
...
...
---
DISABLE / ENABLE
---
DISABLE / ENABLE
---
...
---
DIRECT / REVERSE
---
...
---
SKIP / CHANGE
---
...
...
... (**)
...
... (**)
---
DISABLE / ENABLE
...
... (**)
s
0...9999
---
LIGHT / SERIOUS
%
0...100
%
0...100
---
NO / YES
...
... (**)
...
... (**)
---
DISABLE / ENABLE
...
... (**)
s
0...9999
---
LIGHT / SERIOUS
...
...
---
DISABLE / ENABLE
---
DISABLE / ENABLE
---
...
---
...
---
SKIP / CHANGE
---
...
---
LIGHT / SERIOUS
s
0...9999
...
...
---
DISABLE / ENABLE
---
NO / YES
---
...
---
MON, ..., SUN
...
...
...
...
...
...
---
---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
---
MONDAY...SUNDAY; MON-FRI;
MON-SAT; SAT&SUN; ALL DAYS
---
°C; °F; barg; psig; %; ppm -
...
...
---
---, B1...B10 (****)
---
... (**)
...
... (**)
...
... (**)
...
... (**)
...
... (**)
...
...
---
---, 01...18, B1...B10 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
...
...
---
---, 01...29 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active
...
...
---
---, 01...06 (****)
FCS1*-CONVONOFF; "-----";"
---
MCHRTF*";" FCS3*-CONV010"
%
0.0...100.0
...
...
---
---, 01...18, B1...B10 (****)
---
Closed / Open
---
NC / NO
---
Not active / Active

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents