Mask index
Display description
Confi g. action 1
---
Cad12
Confi g. action 2
---
Enable supervisor action
Enable
Load
Cad13
Voltage
Cos(phi)
Reset counter
Number of alarms for
Cae01
each compressor
Alarm1 description
Cae02
Alarm1 description (*)
Cae03
Activ.delay
Start up delay
Cae04
Reset
Priority
...
...
Suction pressure/tempe-
Cae24
rature high alarm
Threshold
Alarm diff .
Cae25
Alarm delay
Suction pressure/tempe-
Cae26
rature low alarm
Threshold
Alarm diff .
Cae27
Alarm delay
Enable oil temperature
alarm management (*)
Cae28
Enable discharge temp.
alarm management (*)
Low superheat alarm
threshold
Alarm diff .
Cae29
Switch OFF comp.
Reset
Alarm delay
Time of semi-automatic
alarm evaluation
Cae30
N° of reties before alarm
becomes manual
Switch off comp.1
Cae40
Reset
Alarm delay
Compressors type
Caf02
Compressors number
Cmp1,...
Caf03
Refrigerant type
Caf04
Min on time
Min off time
Caf05
Min time to start same
compressor
Ignition type
Caf06
Star time
Caf07
Star line delay
Star delta delay
Caf08
Partwinding delay
Equalization
Caf09
Equalizat.time
Description
Confi guration of action associated with the fi rst digital input connected
to pLoads (line 1)
Percentage value to limit capacity to or reduce capacity by if the ''LIMIT
CAPACITY TO'' or ''LIMIT CAPACITY BY'' actions have been confi gured
respectively (line 1)
Confi guration of action associated with the second digital input con-
nected to pLoads (line 1)
Percentage value to limit capacity to or reduce capacity by if the ''LIMIT
CAPACITY TO'' or ''LIMIT CAPACITY BY'' actions have been confi gured
respectively (line 1)
Enable pLoads action from supervisor (line 1)
Enable calculation of power consumption
Number of phases
Mains voltage
Displacement (cosφ)
Reset current power counter
Number of alarms for each compressor (line 1)
Selection of the fi rst compressor alarm description: Generic, Overload,
High pressure, Low pressure, Oil (line 1)
Selection of the fi rst compressor alarm description: Rotation, Oil warning
(line 1)
Activation delay for compressor alarm 1 during working (line 1)
Activation delay for compressor alarm 1 at start up (line 1)
Type of reset for compressor alarm 1 (line 1)
Type of priority for compressor alarm 1 (line 1)
...
Type of high suction pressure/temperature alarm threshold
High suction pressure/temperature alarm threshold
High suction pressure/temperature alarm diff erential
High suction pressure/temperature alarm delay
Type of low suction pressure/temperature alarm threshold
Low suction pressure/temperature alarm threshold
Low suction pressure/temperature alarm diff erential
Low suction pressure/temperature alarm delay
Enable Digital Scroll oil temperature alarm (line 1)
Enable Digital Scroll discharge temperature alarm (line 1)
Threshold for low superheat alarm (line 1)
Low superheat alarm diff erential (line 1)
Enable compressor off for low superheat alarm (line 1)
Type of low superheat alarm reset (line 1)
Low superheat alarm delay (line 1)
Time of semi-automatic alarm evaluation for screw compressors out
of envelope (line 1)
Number of retries before alarm becomes manual (line 1)
Enable compressor 1 off for compressor inverter warning (line 1)
Type of compressor inverter warning reset (line 1)
Compressor inverter warning activation delay (line 1)
Type of compressors (line 1)
Number of compressors (line 1)
Enable compressors (line 1)
Type of refrigerant (suction Line 1)
Minimum compressor on time (line 1)
Minimum compressor off time (line 1)
Minimum time between same compressor starts (line 1)
Type of compressors start up
Star relay run time
Delay between star and line relay
Delay between star and delta relay
Partwinding delay
Enable compressors equalization at start up
Equalization duration
Default
NO ACTION ---
0.0
NO ACTION ---
0.0
NO
NO
SINGLE-
PHASE
400
1.0
NO
1/4 (*)
...
...
0
0
AUT.
SERIOUS
...
ABSOLUTE
... (**)
... (**)
120
ABSOLUTE
... (**)
... (**)
30
NO
NO
3,0
1,0
NO
MANUAL
30
2
3
NO
MANUAL
0
RECIPROCA-
TING
2/3 (*)
DIS
R404A
30
120
360
DIRECT
0
0
0
0
NO
0
59
ENG
UOM
Values
NO ACTIONLIMIT TO CURRENT
CAPACITYLIMIT CAPACITY
TODEC. CAPACITY BY
%
0.0 to 100.0
NO ACTIONLIMIT TO CURRENT
CAPACITYLIMIT CAPACITY
TODEC. CAPACITY BY
%
0.0 to 100.0
---
NO / YES
---
NO / YES
---
SINGLE-PHASE/THREE-PHASE
V
0 to 999
---
0.0 to 1.0
---
NO / YES
---
0...4/7 (*)
---
(Not available)
(Not selected)
(Selected)
---
(Not available)
(Not selected)
(Selected)
s
0...999
s
0...999
---
AUT. / MAN.
---
LIGHT / SERIOUS
...
...
---
ABSOLUTE / RELATIVE
...
... (**)
...
... (**)
s
0...999
---
ABSOLUTE / RELATIVE
...
... (**)
...
... (**)
s
0...999
---
NO / YES
---
NO / YES
K
0.0...99.9
K
0.0...9,9
---
NO / YES
---
MANUAL / AUTO
s
0...999
min
0...999
---
0...9
---
NO / YES
---
MANUAL/AUTO
s
0...999
---
RECIPROCATING
SCROLL
SCREW
---
1...6/12 (*)
---
DIS / EN
---
R22 - R134a - R404A - R407C -
R410A - R507A - R290 - R600 -
R600a - R717 -R744 - R728 -
R1270 - R417A - R422D -R413A -
R422A - R423A - R407A - R427A
- R245Fa - R407F - R32
s
0...999
s
0...999
s
0...999
---
DIRECT
PART WINDING
STAR DELTA
ms
0...9999
ms
0...9999
ms
0...9999
ms
0...9999
---
NO / YES
s
0...999
pRack +0300025EN rel. 1.3 - 17.12.2015