Analogue Outputs Y...; Digital Outputs No..., Nc...; Ssr Outputs (In Models Where Featured) - Carel PRK300L3FK User Manual

Prack pr300 no power & signal cables together read carefully in the text! compressor rack controller
Table of Contents

Advertisement

2.2.6

Analogue outputs Y...

Type
0 to 10 V optically-isolated on Y1...Y6
Lmax
30 m
SMALL, MEDIUM/ BUILT-IN DRIVER
Maximum number
LARGE
Power supply
external
Precision
Y1...Y6
Resolution
8 bit
Settling time
Y1...Y6
Maximum load
1 kΩ (10 mA)
Warnings:
for lengths > 10 m, only use shielded cable, with the shield connected to earth;
a 0 to 10 Vdc analogue output can be connected in parallel to other outputs of the same type, or alternatively to an external source of voltage. The higher
voltage will be considered. Correct operation is not guaranteed if actuators with voltage inputs are connected;
power the VG-VG0 analogue outputs at the same voltage on G-G0: Connect G0 to VG0 and G to VG. This is valid for both alternating and direct current
power supplies.
2.2.7

Digital outputs NO..., NC...

Type
Relay. Minimum contact current: 50 mA.
Maximum no
8: SMALL; 13: MEDIUM/ BUILT-IN DRIVER; 18: LARGE;
The relay outputs have diff erent features depending on the model of controller. The outputs can be divided into groups. The relays belonging
to the same group (individual cell in the table) have basic insulation and therefore must have the same voltage. Between groups (cells in the
Insulation distance
table) there is double insulation and consequently these may have diff erent voltages. There is also double insulation between each terminal of
the digital outputs and the rest of the controller.
Model
SMALL
Type of relay
MEDIUM/ BUILT-IN DRIVER
Makeup of the
Type of relay
groups
LARGE NO
Type of relay
LARGE NC
Type of relay
Number of
1: SMALL (relay 8)
changeover
3: MEDIUM (relay 8, 12, 13)
contacts
5: LARGE NO/NC (relay 8, 12, 13, 14 e 15)
Note: the output relays have diff erent features, depending on the model of controller.
Relay type A
Switchable power
Relay type B
Relay type C
2.2.8

SSR outputs (in models where featured)

Maximum number
Working voltage
Load current (MAX)
Impulsive load current (MAX)
Warnings:
if the load requires higher current, use an external SSR;
to power external resistive loads via SSRs, use the same power supply as the pRack (supplied to terminals G-G0), which must be dedicated and not shared by other
devices (contactors, coils, etc..);
the groups that the digital outputs are divided into have two common pole terminals to simplify wiring;
make sure that the current running through the common terminals does not exceed the rated current of an individual terminal, that is, 8 A.
1
2
1...3
4...6
Type A
Type A
1...3
4...6
Type A
Type A
1...3
4...6
Type A
Type A
1...3
4...6
Type A
Type A
Rated data
SPDT, 2000 VA, 250 Vac, 8A resistive
UL 873
Approval
EN 60730-1
Relay rated data
SPST, 1250 VA, 250 Vac, 5A resistive
UL 873
Approval
EN 60730-1
Relay rated data
SPDT, 1250 VA, 250 Vac, 5A resistive
UL 873
Approval
EN 60730-1
2: SMALL (ouputs 7, 8); 2: MEDIUM (ouputs 7, 12); 6: LARGE (ouputs 7, 8, 12, 13, 14, 15)
24 Vac/Vdc
1 A
1.2 A
4
Y1...Y4, 0 to 10 V
6
Y1...Y6, 0 to 10 V
24 Vac (+10/-15%) or 28 to 36 Vdc on VG(+), VG0(-)
± 2% full scale
from 1 s (slew rate 10 V/s) to 20 s (slew rate 0.5 V/s) selectable via SW
Relays with the same insulation
Group
3
4
5
6
7
8
-
-
Type A
Type A
-
-
7
8
9...11
12
Type A
Type A
Type A
Type A
7
8
9...11
12
Type A
Type A
Type A
Type A
7
8
9...11
12
Type A
Type A
Type A
Type A
2 A 250 Vac resistive, 2A FLA, 12 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
2 A resistive, 2A inductive, cosφ=0.6, 2(2)A (100,000 cycles)
1 A 250 Vac resistive, 1A FLA, 6 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
1 A resistive, 1A inductive, cosφ=0.6, 1(1)A (100,000 cycles)
1 A 250 Vac resistive, 1A FLA, 6 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
1 A resistive, 1A inductive, cosφ=0.6, 1(1)A (100,000 cycles)
13
7
8
9
10
-
-
-
-
-
-
-
-
13
-
-
-
Type A
-
-
-
13
14...15
16...18
-
Type A
Type A
Type A
-
13
14...15
16...18
-
Type A
Type A
Type C
-
pRack +0300025EN rel. 1.3 - 17.12.2015
ENG
Tab. 2.i
11
-
-
-
-
-
-
-
-
Tab. 2.a
Tab. 2.j

Hide quick links:

Advertisement

Table of Contents
loading