Swann AMI Powercon Operator's Manual page 80

Table of Contents

Advertisement

AMI Powercon
Program List and Explanations
5.2.1.43
5.2.1.43.10
5.2.1.43.20
5.2.1.43
5.2.1.43.11
5.2.1.43.21
5.2.1.43
5.2.1.43.12
5.2.1.43.22
5.2.1.43
5.2.1.43.13
5.2.1.43.23
5.2.1.43.3
5.2.1.43.4
5.2.1.43.5
78
Control upwards or downwards
Setpoint: User-defined process value for the selected parameter.
P-Band: Range below (upwards control) or above (downwards con-
trol) the set-point, within the dosing intensity is reduced from 100%
to 0% to reach the setpoint without overshooting.
Control Parameters: if Parameters = Conductivity
Setpoint
Range: 0 S–300 mS
P-Band:
Range: 0 S–300 mS
Control Parameters: if Parameters = Temperature
Setpoint
Range: -25 to +270 °C
P-Band:
Range: 0 to +100 °C
Control Parameters: if Parameters = Sample flow
Setpoint
Range: 0 –50 l/h
P-Band:
Range: 0 –50 l/h
Control Parameters: if Parameters = Cond. uc.
Setpoint
Range: 0 S–300 mS
P-Band:
Range: 0 S–300 mS
Reset time: The reset time is the time till the step response of a sin-
gle I-controller will reach the same value as it will be suddenly
reached by a P-controller.
Range: 0–9'000 sec
Derivative time: The derivative time is the time till the ramp re-
sponse of a single P-controller will reach the same value as it will
be suddenly reached by a D-controller.
Range: 0–9'000 sec
Control timeout: If a controller action (dosing intensity) is constantly
over 90% during a defined period of time and the process value
does not come closer to the setpoint, the dosing process will be
stopped for safety reasons.
Range: 0–720 min
A-96.250.341 / 061015

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents