CO2 sensor, 2 PID setpoints

7.8 CO2 sensor, 2 PID setpoints
Macro 112 "CO2 sensor, 2 PID setpoints"
ON/OFF and PID setpoint selection via DI0 or DI2
Set the fixed setpoint (50 % corresponding to the
CO2 equivalent 1000 ppm)
External alarm at DI1. The fan is stopped.
Error message: Digital output 0
Status display: Digital output 2
If DI0 and DI2 are active simultaneously, the
setpoints are added. The drive starts when one of
the inputs is in ON position.
Parameter
Value
p756[0]
0
p840[0]
r2225.0
p1113[0]
0
p2103[0]
0
p2106[0]
r722.1
p2200[0]
1
p2201[0]
50
p2203[0]
10
p2220[0]
r722.0
p2222[0]
r722.2
p2253[0]
r2224
p2264[0]
r755[0]
p2267
120%
p2268
-10%
p2306
1
74 | 98
Siemens
Building Technologies
Description
Unipolar voltage input (0...10 V)
ON / OFF (OFF1)
Setpoint inversion
BI: 1. Acknowledge faults
External fault
Technology controller enable
Technology controller fixed value 1
Technology controller fixed value 3
BI: Technology controller fixed value selection bit 0
BI: Technology controller fixed value selection bit 2
Technology controller setpoint 1
Technology controller actual value
Technology controller upper limit actual value
Technology controller lower limit actual value
Technology controller fault-signal inversion
A5E36496664A_d