Commissioning
6
Additional settings
62 | 98
Siemens
Building Technologies
Parameter
Factory
Function
settings
p0756 [0]
-
AI 0 (0-4)
p0756 [1]
-
AI 1 (0-4)
p0756 [2]
-
AI 2 (2-3, 6-8)
p0756 [3]
-
AI 3 (6-8)
p0771[0]
-
AO 0
p0771[1]
-
AO 1
p0776[0, 1]
-
Analog outputs, type
0: Current output (0 mA...20 mA)
1: Voltage output (0 V...10 V)
2: Current output (4 mA...20 mA)
p0840
r0722.0
ON/OFF1 signal source
p0852
1
Enable operation
Is used to let the motor coast to a standstill if the ON command is
enabled. Example: P0852 = r0722.0.
p1000
2
Speed setpoint selection
2 = Analog setpoint
3 = Fixed speed
6 = Fieldbus
For further values, see the List Manual
p1082
1500 rpm
Maximum motor speed in rpm
2-pole motor (rated
speed approx. 2750
– 3000 rpm)
4-pole motor (rated
speed approx. 1250
– 1500 rpm)
The reference speed (p2000) must be set to the same value.
p1113
r722.1
Invert direction of rotation
p1200
0
Flying restart selection:
0: Flying restart inactive
1: Flying restart always active (start in setpoint direction)
4: Flying restart always active (start only in setpoint direction)
0: Unipolar voltage input (0 V...10 V)
1: Unipolar voltage input monitored (2 V... 10 V)
2: Unipolar current input (0 mA...20 mA)
3: Unipolar current input monitored (4 mA...20 mA)
4: Bipolar voltage input (-10 V...10 V)
6: LG-Ni1000 temperature sensor (-50 °C...150 °C)
7: PT1000 temperature sensor (-50...250 °C)
8: No sensor connected
Important status signals:
0: Analog output locked
21: Speed actual value
24: Output frequency, smoothed
25: Output voltage smoothed
26: DC link voltage, smoothed
27: Actual current value (smoothed absolute value)
50Hz =
60Hz =
70Hz =
3000 rpm
3600 rpm
4200 rpm
1500 rpm
1800 rpm
2100 rpm
80Hz =
4800 rpm
2400 rpm
A5E36496664A_d