USS protocol
Parameter
Description
p0015
Select value 108 "USS fieldbus" during basic commissioning.
p2020
Value
4
5
6
7
8
9
10
11
12
13
p2021
Valid USS addresses: 1...30
Invalid USS addresses: 0.31...127
p2022
Fieldbus interface USS PZD number
●
Setting the number of 16-bit words in the PZD part of the USS telegram
p2023
Fieldbus interface USS PKW number
●
Setting the number of 16-bit words in the PKW part of the USS telegram
0
3
4
127
Modbus RTU protocol
Parameter
Description
p0015
Select value 109 "Modbus RTU" during basic commissioning.
p2021
Valid Modbus RTU addresses: 1...247
Invalid Modbus RTU address: 0
p2020
Fieldbus baud rate
●
Baud rates from 4800 bps to 187500 bps can be set for communication.
●
Factory setting: 19200 bps
p2024
Modbus timing
●
Index 0: Maximum slave telegram processing time
Maximum response time from the slave to the master.
●
Index 1: Character delay time
Maximum permissible delay time between the individual characters in the
Modbus frame (Modbus standard processing time for 1.5 bytes).
●
Index2: Inter-telegram delay
Maximum permissible delay time between Modbus telegrams (Modbus
standard processing time for 3.5 bytes).
p2029
Fieldbus error statistics
●
Displays receive errors on the fieldbus interface.
P2031
Modbus parity
p2040
Process data monitoring time [ms]
●
Setting the time to monitor the process data received. If no process data is
received within this time, an appropriate message is output
●
Factory setting: 100 ms
●
The setting 0 ms deactivates the monitoring function.
Commissioning
Configuring communication
Baud rate
2400
4800
9600
19200
38400
57600
76800
93750
115200
187500
0 Wörter
3 Wörter
4 Wörter
Variable Anzahl Wörter
A5E36496664A_d
6
57 | 98