Service, maintenance and fault rectification
8
Fault rectification
86 | 98
Siemens
Building Technologies
Number
Cause
F30002
Power unit: DC-link voltage
overvoltage
F30003
Power unit: DC-link voltage
undervoltage
F30004
Drive overtemperature
F30005
I2t drive overload
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30022
Power Module: UCE
monitoring
F30027
Time monitoring for DC-link
pre-charging
Overtemperature, intake air 1.
F30035
F30036
Overtemperature, inside
area
F30037
Rectifier overtemperature
F30052
Incorrect Power Module
data
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in Power
Module
F30059
Internal fan defective
Solution
1.
Increase the ramp-down time (p1121).
2.
Set the rounding times (p1130, p1136).
3.
Activate the DC link voltage controller (p1240,
p1280).
4.
Check the line voltage (p0210).
5.
Check the line phases.
1.
Check the line voltage (p0210).
2.
Check the line phases.
1.
Check whether the drive fan is running.
2.
Check the ambient temperature.
3.
Check whether the motor is overloaded.
4.
Reduce the pulse frequency.
1.
Check the rated currents of the motor and Power
Module.
2.
Reduce the current limit p0640.
3.
When operating with V/f characteristic: Reduce
p1341.
1.
Check the drives's input fuses.
2.
Check the motor cables.
1.
Check the motor cables.
2.
Increase the ramp-up or ramp-down time (p1120).
1.
Check the power cable connections.
2.
Check the motor.
3.
Check the current transducer.
4.
Check the cables and contacts of the brake
connection (a wire might be broken).
1.
Check the Power Module.
2.
Replace the Power Module, if necessary.
1.
Check the supply voltage at the input terminals.
2.
Check the line voltage setting (p0210).
Check whether the fan is running.
2.
Check the fan elements.
3.
Check the ambient temperature.
1.
Check whether the fan is running.
2.
Check the fan elements.
3.
Check the ambient temperature.
4.
Check the motor load.
5.
Check the line phases.
1.
Replace the Power Module.
2.
Update the CU firmware.
1.
Switch the CU off and on again.
2.
Update the firmware.
3.
Contact Technical Support.
1.
Switch the CU off and on again.
2.
Update the firmware.
3.
Contact Technical Support.
1.
Replace the Power Module.
2.
Contact Technical Support.
Check the internal fan and replace it, if necessary.
A5E36496664A_d