Siemens G120P Technical Manual page 63

Variable speed drive
Table of Contents

Advertisement

Siemens
Building Technologies
Parameter
Factory
Function
settings
p1210
0
Automatic restart:
0: Disables automatic restart
1: Acknowledges all faults without restarting
4: Restart after power failure, without additional startup attempts
6: Restart after fault with additional startup attempts
14: Restart after power failure after manual acknowledgement
16: Restart after fault after manual acknowledgement
26: Acknowledging all faults and restarting for an ON command
Recommended setting: 26
During the restart waiting time, the alarm A07321 appears at FW < 4.6.
p1213[0]
60s
Restart monitoring time:
Set this value to 0s for FW < 4.6; otherwise the fault F07320 is output if
there has been no enable.
p1300
2
Open-loop/closed-loop control operating mode:
0: V/f control with linear characteristic
1: V/f control with linear characteristic and FCC
2: V/f control with parabolic characteristic
4: V/f control with linear characteristic and ECO
7: V/f control for parabolic characteristic and ECO
20: Speed control (without encoder)
p1820
0
Change the direction of rotation of the motor:
0: Off
1: On
p1800
4 kHz
Pulse frequency
p1900
0
Motor data identification:
0: Disabled
1: Motor data identification at standstill and when the motor is rotating
2: Motor data identification at standstill
3: Motor data identification when the motor is rotating
It is imperative that this is carried out when using SLVC (P1300 = 20).
p2000
1500 rpm
Reference speed relative to 100% setpoint, identical to P1082
p2103
r722.2
Acknowledge faults
p3880
0
ESM activation of the signal source via digital input
p3881
0
ESM setpoint source:
0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Analog setpoint AI0 (r0755[0])
3: Setpoint from the fieldbus
4: Setpoint from the technology controller
6: Enable OFF1 reaction
7: Enable OFF2 reaction
p8400
0
Time of real-time clock:
[0] = Hours (0 ... 23)
[1] = Minutes (0 ... 59)
[2] = Seconds (0 ... 59)
Commissioning
6
Additional settings
63 | 98
A5E36496664A_d
2016-03-17