Figure 24: EMC-compliant wiring IP55
Item
Designation
1
Strain relief
2
Line supply cable, unshielded
3
Good conductive connection for high-
frequency EMC interference
4
Standard cable gland
5
EMC gland
6
Shielded motor cable
Use a shielded cable for terminal wiring of the Control Unit.
Use either the screening termination kit of the Control Unit or an EMC cable
gland to bond the shield.
Expose the motor cable shield at the point where the cable is fed through the
base plate and ensure that it is in complete contact with an EMC cable gland. It
is important for the shield to be fed through the cable gland and then to be
connected at the designated place inside the enclosure once again. This
ensures that both the gland plate and the enclosure are in contact with the
shield.
Feed the motor cable through the right-hand opening in the gland plate.
EMC-compliant installation (examples)
Item
Designation
7
EMC gland (essential for Class B filters)
8
Shielding
9
Motor cable shield
10
Shield bonded over large area
11
Control Unit control cable
Installing