The configuration workload can be reduced by leaving out values which are not
required. In this case, the appropriate parameters must be set manually. For more
information, refer to table "Fieldbus control word".
P1 FLN
Parameter
Value
p0015
114
p2020
5
p2021
1 ... 99
The "Point numbers" defined in the device for communication via P1 can be found
in the Operating Instructions for the Control Unit (A5E34257946A AB).
Fieldbus control word
r2090
BACnet
Bit 0
BV20
Bit 1
BV27
Bit 2
BV28
Bit 3
BV26
Bit 4
BV26
Bit 5
BV26
Bit 6
BV26
Bit 7
BV22
Bit 8
N/A
Bit 9
N/A
Bit 10
BV93
Bit 11
BV21
Bit 12
N/A
Bit 13
N/A
Bit 14
N/A
Bit 15
N/A
Description
Select value 114 "P1 communication" during basic commissioning.
Baud rate 4800 bps, alternative setting option for P1: p2020 = 6 (9600
bps)
Slave address (factory setting = 99)
Function
Command execution
No OFF2
No OFF3
Enable operation
Permit RFG enable
Enable RFG
Enable setpoint
Acknowledge faults
Reserved
Reserved
Master control by PLC
Inversion direction
Reserved
MOP setpoint higher
MOP setpoint lower
Reserved
Commissioning
Configuring communication
Parameter
Condition for
motor start
p0840
1
p0844
1
p0848
1
p0852
1
p1140
1
p1141
1
p1142
1
p2103
-
-
-
-
-
p0854
1
p1113
-
-
-
p1035
0
p1036
0
-
-