The control panel supports telephone (PSTN) communications with the plug-in telephone
communicator (B430).
7.1

B430 Plug-in Communicator, Telephone

The B430 provides communication over PSTN. The module provides a single telephone
interface RJ-45 connector for connecting the phone line. The module plugs directly into the
control panel with no additional connections required.
The control panel supports one plug-in module plugged directly into the control panel board.
The module plugs into a connector and is held in place with a plug-in module retention clip.
The module handle and support on top of the module hold the unit during installation.
For detailed instructions, refer to the corresponding document listed in Related
documentation, page 12.
Notification
The B430 module by Bosch Security Systems, Inc. is registered with the Federal
Communication Commission (FCC) under Part 68, for connection to the public telephone
system using an RJ31X or RJ38X phone line connection jack installed by the local telephone
company.
Do not connect registered equipment to party lines or coin-operated telephones. Notify the
local telephone company and provide the following information before connecting the control
panel to the telephone network:
7.1.1

Supervision

The control panel supervises the phone line. You can configure the supervision time using RPS
or the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and
China).
7.1.2

Installation and module wiring (B430)

Calculate power consumption
Make sure that there is enough power for the module and the other powered devices that you
want to connect to the system.
Refer to On-board outputs, page 49.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Installing the module
1.
2.
3.
4.
2018.07 | 16 | F.01U.287.180
The particular line to which you connect the module
Make (Bosch Security Systems, Inc.), model (B6512/B5512/B4512/B3512), and serial
number of the control panel
FCC registration number: ESVAL00BB430
Ringer eq: 0.0B
Align the module with the on-board plug-in connector on the control panel.
The retention clip has a locking device to help hold the card in position. Pull the locking
device back.
Align the PCB metal contacts with the on-board connector.
Push the module into place. The retention clip snaps closed to hold the module in
position.