2.2 SPECIFICATIONS
IRIG-B OUTPUT
Amplitude:
Maximum load:
Time delay:
Isolation:
CONTROL POWER EXTERNAL OUTPUT
2
(FOR DRY CONTACT INPUT)
Capacity:
Isolation:
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
Standard output points: 32
User output points:
RS232
Front port:
RS485
1 or 2 rear ports:
Typical distance:
Isolation:
2-16
10 V peak-peak RS485 level
100 ohms
1 ms for AM input
40 μs for DC-shift input
2 kV
100 mA DC at 48 V DC
±300 Vpk
32
®
19.2 kbps, Modbus
RTU
®
Up to 115 kbps, Modbus
RTU, isolated
together at 36 Vpk
1200 m
2 kV
D60 Line Distance Relay
2 PRODUCT DESCRIPTION
DIRECT OUTPUTS
Output points:
32
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 kΩ for –1 to 1 mA range
12 kΩ for 0 to 1 mA range
600 Ω for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
0.001
ETHERNET (FIBER)
PARAMETER
10MB MULTI-
MODE
Wavelength
820 nm
Connector
ST
Transmit power
–20 dBm
Receiver sensitivity
–30 dBm
Power budget
10 dB
Maximum input
–7.6 dBm
power
Typical distance
1.65 km
Duplex
full/half
Redundancy
yes
ETHERNET (COPPER)
Modes:
10 MB, 10/100 MB (auto-detect)
Connector:
RJ45
SNTP clock synchronization error: <10 ms (typical)

2.2.8 COMMUNICATIONS

FIBER TYPE
100MB MULTI-
100MB SINGLE-
MODE
MODE
1310 nm
1310 nm
ST
SC
–20 dBm
–15 dBm
–30 dBm
–30 dBm
10 dB
15 dB
–14 dBm
–7 dBm
2 km
15 km
full/half
full/half
yes
yes