APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 28 of 48)
ADDR
REGISTER NAME
77D0
...Repeated for RTD Input 42
77E0
...Repeated for RTD Input 43
77F0
...Repeated for RTD Input 44
7800
...Repeated for RTD Input 45
7810
...Repeated for RTD Input 46
7820
...Repeated for RTD Input 47
7830
...Repeated for RTD Input 48
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F06
Neutral Overvoltage 1 Target
7F07
Neutral Overvoltage 1 Events
7F08
Neutral Overvoltage 1 Curves
7F09
Reserved (8 items)
7F10
...Repeated for Neutral Overvoltage 2
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30
Auxiliary Overvoltage 1 Function
7F31
Auxiliary Overvoltage 1 Signal Source
7F32
Auxiliary Overvoltage 1 Pickup
7F33
Auxiliary Overvoltage 1 Pickup Delay
7F34
Auxiliary Overvoltage 1 Reset Delay
7F35
Auxiliary Overvoltage 1 Block
7F36
Auxiliary Overvoltage 1 Target
7F37
Auxiliary Overvoltage 1 Events
7F38
Reserved (8 items)
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0A
Digital Element 1 Pickup Delay
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3.00
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 3
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
2 to 90
---
0 to 1
---
0 to 65535
0 to 999999.999
D60 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F116
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
---
---
F300
---
1
F102
---
---
F203
---
1
F300
s
0.001
F003
DEFAULT
B
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Definite Time)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0
0
0
0 (Disabled)
"Dig Element 1"
0
0
B-35