B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 48)
ADDR
REGISTER NAME
6844
PUTT 1P Rx1
6845
PUTT 1P Rx2
6846
PUTT 1P Rx3
6847
PUTT 1P Rx4
6848
PUTT 1P Target
B
6849
PUTT 1P Event
684A
Reserved (6 items)
Pilot POTT (1P) (Read/Write Setting)
6850
POTT 1P Scheme Function
6851
POTT 1P Permissive Echo
6852
POTT 1P Rx Pickup Delay
6853
POTT 1P Trans Block Pickup Delay
6854
POTT 1P Trans Block Reset Delay
6855
POTT 1P Echo Duration
6856
POTT 1P Echo Lockout
6857
POTT 1P Line End Open Pickup Delay
6858
POTT 1P Seal In Delay
6859
POTT 1P Ground Directional Overcurrent Forward
685A
POTT 1P Number of Communication Bits
685B
POTT 1P Rx1
685C
POTT 1P Rx2
685D
POTT 1P Rx3
685E
POTT 1P Rx4
685F
POTT 1P Target
6860
POTT 1P Event
6861
POTT 1P Echo Condition
6862
Reserved (6 items)
Pilot Hybrid POTT (1P) (Read/Write Setting)
6868
Hybrid POTT 1P Scheme Function
6869
Hybrid POTT 1P Permissive Echo
686A
Hybrid POTT 1P Rx Pickup Delay
686B
Hybrid POTT 1P Trans Block Pickup Delay
686C
Hybrid POTT 1P Trans Block Reset Delay
686D
Hybrid POTT 1P Echo Duration
686E
Hybrid POTT 1P Echo Lockout
686F
Hybrid POTT 1P Seal In Delay
6870
Hybrid POTT 1P Ground Directional Overcurrent Forward
6871
Hybrid POTT 1P Gnd Directional Overcurrent Reverse
6872
Hybrid POTT 1P Number of Communication Bits
6873
Hybrid POTT 1P Rx1
6874
Hybrid POTT 1P Rx2
6875
Hybrid POTT 1P Rx3
6876
Hybrid POTT 1P Rx4
6877
Hybrid POTT 1P Target
6878
Hybrid POTT 1P Event
6879
Hybrid POTT Echo Condition
687A
Hybrid POTT Weak Infeed
687B
Hybrid POTT Weak Infeed Condition
687C
Reserved (4 items)
Pilot Blocking (1P) (Read/Write Setting)
6880
Blocking Scheme 1P Function
6881
Block 1P Rx Coord Pickup Delay
6882
Block 1P Transient Block Pickup Delay
6883
Block 1P Transient Block Reset Delay
B-28
RANGE
UNITS
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 2
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 1
0 to 2
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65535
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 2
0 to 65535
0 to 1
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
D60 Line Distance Relay
APPENDIX B
STEP
FORMAT
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
0 (Disabled)
---
1
F001
---
1
F102
0 (Disabled)
---
1
F199
0 (Disabled)
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
0 (Disabled)
---
1
F300
---
1
F001
---
1
F102
0 (Disabled)
---
1
F199
0 (Disabled)
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
0.001
F001
---
1
F300
---
1
F300
---
1
F198
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
0 (Disabled)
---
1
F300
---
1
F199
---
1
F300
---
1
F001
---
1
F102
0 (Disabled)
s
0.001
F001
s
0.001
F001
s
0.001
F001
DEFAULT
0
0
0
0
0
0
20
90
100
250
50
0
0
0 (1)
0
0
0
0
0
0
0
20
90
100
250
0
0
0
0 (1)
0
0
0
0
0
1 (Enabled)
0
0
10
30
90