Advertisement

5.4 FLEXLOGIC™
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–6: D60 FLEXLOGIC™ OPERANDS (Sheet 1 of 8)
OPERAND TYPE
OPERAND SYNTAX
CONTROL
CONTROL PUSHBTN n ON
PUSHBUTTONS
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIRECT INPUT/
DIR IO CH1(2) CRC ALARM
OUTPUT
CHANNEL
DIR IO CRC ALARM
MONITORING
DIR IO CH1(2) UNRET ALM
DIR IO UNRET ALM
ELEMENT:
AR ENABLED
Autoreclose
AR DISABLED
(1P/3P)
AR RIP
AR 1-P RIP
AR 3-P/1 RIP
AR 3-P/2 RIP
AR 3-P/3 RIP
AR 3-P/4 RIP
AR LO
AR BKR1 BLK
AR BKR2 BLK
AR CLOSE BKR1
5
AR CLOSE BKR2
AR FORCE 3-P TRIP
AR SHOT CNT > 0
AR SHOT CNT = 1
AR SHOT CNT = 2
AR SHOT CNT = 3
AR SHOT CNT = 4
AR ZONE 1 EXTENT
AR INCOMPLETE SEQ
AR RESET
ELEMENT:
AUX OV1 PKP
Auxiliary
AUX OV1 DPO
Overvoltage
AUX OV1 OP
ELEMENT:
AUX UV1 PKP
Auxiliary
AUX UV1 DPO
Undervoltage
AUX UV1 OP
ELEMENT:
DIR BLOCK TX INIT
Blocking Scheme
DIR BLOCK TX1 STOP
DIR BLOCK TX2 STOP
DIR BLOCK TX3 STOP
DIR BLOCK TX4 STOP
DIR BLOCK TRIP A
DIR BLOCK TRIP B
DIR BLOCK TRIP C
DIR BLOCK TRIP 3P
DIR BLOCK OP
ELEMENT:
BKR ARC 1 OP
Breaker Arcing
BKR ARC 2 OP
ELEMENT
BKR FAIL 1 RETRIPA
Breaker Failure
BKR FAIL 1 RETRIPB
BKR FAIL 1 RETRIPC
BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
BKR FAIL 1 T2 OP
BKR FAIL 1 T3 OP
BKR FAIL 1 TRIP OP
BKR FAIL 2
5-60
OPERAND DESCRIPTION
Control Pushbutton n (n = 1 to 7) is being pressed.
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of Direct Input messages received on Channel 1(2) and failing the
CRC exceeded the user-specified level.
The rate of Direct Input messages failing the CRC exceeded the user-
specified level on Channel 1 or 2.
The rate of returned direct input/output messages on Channel 1(2) exceeded
the user-specified level (ring configurations only).
The rate of returned direct input/output messages exceeded the user-
specified level on Channel 1 or 2 (ring configurations only).
Autoreclosure is enabled and ready to perform
Autoreclosure is disabled
Autoreclosure is in "Reclose in Progress" state
A single-pole reclosure is in progress
A three-pole reclosure is in progress, via Dead Time 1
A three-pole reclosure is in progress, via Dead Time 2
A three-pole reclosure is in progress, via Dead Time 3
A three-pole reclosure is in progress, via Dead Time 4
Autoreclosure is in lockout state
Reclosure of Breaker 1 is blocked
Reclosure of Breaker 2 is blocked
Reclose Breaker 1 signal
Reclose Breaker 2 signal
Force any trip to a three-phase trip
The first 'CLOSE BKR X' signal has been issued
Shot count is equal to 1
Shot count is equal to 2
Shot count is equal to 3
Shot count is equal to 4
The Zone 1 Distance function must be set to the extended overreach value
The incomplete sequence timer timed out
AR has been reset either manually or by the reset timer
Auxiliary Overvoltage element has picked up
Auxiliary Overvoltage element has dropped out
Auxiliary Overvoltage element has operated
Auxiliary Undervoltage element has picked up
Auxiliary Undervoltage element has dropped out
Auxiliary Undervoltage element has operated
Directional blocking signal is initiated
Directional blocking scheme de-asserts transmit bit no. 1
Directional blocking scheme de-asserts transmit bit no. 2
Directional blocking scheme de-asserts transmit bit no. 3
Directional blocking scheme de-asserts transmit bit no. 4
Directional blocking scheme has operated to trip phase A
Directional blocking scheme has operated to trip phase B
Directional blocking scheme has operated to trip phase C
Directional blocking scheme has tripped all 3 phases
Directional blocking scheme has operated
Breaker Arcing Current 1 has operated
Breaker Arcing Current 2 has operated
Breaker Failure 1 re-trip phase A (only for 1-pole schemes)
Breaker Failure 1 re-trip phase B (only for 1-pole schemes)
Breaker Failure 1 re-trip phase C (only for 1-pole schemes)
Breaker Failure 1 re-trip 3-phase
Breaker Failure 1 Timer 1 is operated
Breaker Failure 1 Timer 2 is operated
Breaker Failure 1 Timer 3 is operated
Breaker Failure 1 trip is operated
Same set of operands as shown for BKR FAIL 1
D60 Line Distance Relay
5 SETTINGS