GE D60 Instruction Manual page 425

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 30 of 48)
ADDR
REGISTER NAME
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement™ 1 Function
9001
FlexElement™ 1 Name
9004
FlexElement™ 1 InputP
9005
FlexElement™ 1 InputM
9006
FlexElement™ 1 Compare
9007
FlexElement™ 1 Input
9008
FlexElement™ 1 Direction
9009
FlexElement™ 1 Hysteresis
900A
FlexElement™ 1 Pickup
900C
FlexElement™ 1 DeltaT Units
900D
FlexElement™ 1 DeltaT
900F
FlexElement™ 1 Pickup Delay
9010
FlexElement™ 1 Reset Delay
9011
FlexElement™ 1 Block
9012
FlexElement™ 1 Target
9013
FlexElement™ 1 Events
9014
...Repeated for FlexElement™ 2
9028
...Repeated for FlexElement™ 3
903C
...Repeated for FlexElement™ 4
9050
...Repeated for FlexElement™ 5
9064
...Repeated for FlexElement™ 6
9078
...Repeated for FlexElement™ 7
908C
...Repeated for FlexElement™ 8
90A0
...Repeated for FlexElement™ 9
90B4
...Repeated for FlexElement™ 10
90C8
...Repeated for FlexElement™ 11
90DC
...Repeated for FlexElement™ 12
90F0
...Repeated for FlexElement™ 13
9104
...Repeated for FlexElement™ 14
9118
...Repeated for FlexElement™ 15
912C
...Repeated for FlexElement™ 16
Fault Report Settings (Read/Write Setting) (5 modules)
9200
Fault Report 1 Source
9201
Fault Report 1 Trigger
9202
Fault Report 1 Z1 Magnitude
9203
Fault Report 1 Z1 Angle
9204
Fault Report 1 Z0 Magnitude
9205
Fault Report 1 Z0 Angle
9206
Fault Report 1 Line Length Units
9207
Fault Report 1 Line Length
9208
...Repeated for Fault Report 2
9210
...Repeated for Fault Report 3
9218
...Repeated for Fault Report 4
9220
...Repeated for Fault Report 5
DCMA Outputs (Read/Write Setting) (24 modules)
9300
dcmA Output 1 Source
9301
dcmA Output 1 Range
9302
dcmA Output 1 Minimum
9304
dcmA Output 1 Maximum
9306
...Repeated for dcmA Output 2
930C
...Repeated for dcmA Output 3
9312
...Repeated for dcmA Output 4
9318
...Repeated for dcmA Output 5
GE Multilin
RANGE
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0.1 to 50
-90 to 90
0 to 2
20 to 86400
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 5
0 to 65535
0.01 to 250
25 to 90
degrees
0.01 to 650
25 to 90
degrees
0 to 1
0 to 2000
0 to 65535
0 to 2
–90 to 90
–90 to 90
D60 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
---
F206
---
1
F600
---
1
F600
---
1
F516
---
1
F515
---
1
F517
%
0.1
F001
pu
0.001
F004
---
1
F518
---
1
F003
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F300
ohms
0.01
F001
1
F001
ohms
0.01
F001
1
F001
---
1
F147
0.1
F001
---
1
F600
---
1
F522
pu
0.001
F004
pu
0.001
F004
DEFAULT
0 (Disabled)
"FxE 1"
0
0
B
0 (LEVEL)
0 (SIGNED)
0 (OVER)
30
1000
0 (Milliseconds)
20
0
0
0
0 (Self-reset)
0 (Disabled)
0 (SRC 1)
0
300
75
900
75
0 (km)
1000
0
0 (–1 to 1 mA)
0
1000
B-37

Advertisement

Table of Contents
loading

Table of Contents