Power Supply; Outputs - GE D60 Instruction Manual

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
LOW RANGE
Nominal DC voltage:
24 to 48 V
Min/max DC voltage:
20 / 60 V
Voltage loss hold-up:
20 ms duration at nominal
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Min/max DC voltage:
88 / 300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Min/max AC voltage:
88 / 265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at nominal
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break (DC inductive, L/R = 40 ms):
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
Operate time:
< 4 ms
Contact material:
silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break at L/R of 40 ms:
0.25 A DC max.
Operate time:
< 4 ms
Contact material:
silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
FORM-A CURRENT MONITOR
Threshold current:
approx. 80 to 100 mA
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
8 A
Break (DC inductive, L/R = 40 ms):
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
Operate time:
< 8 ms
Contact material:
silver alloy
GE Multilin
ALL RANGES
Volt withstand:
Power consumption:
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
DC:
FAST FORM-C RELAY
Make and carry:
Minimum load impedance:
INPUT
VOLTAGE
250 V DC
120 V DC
48 V DC
24 V DC
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load impedance.
Operate time:
Internal Limiting Resistor: 100 Ω, 2 W
SOLID-STATE OUTPUT RELAY
Operate and release time: <100 μs
Maximum voltage:
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
Make and carry:
for 0.2 s:
for 0.03 s
Breaking capacity:
Operations/
interval
Break
capability
(0 to 250 V
DC)
D60 Line Distance Relay
2.2 SPECIFICATIONS

2.2.6 POWER SUPPLY

2 × Highest Nominal Voltage for 10 ms
typical = 15 to 20 W/VA
maximum = 50 W/VA
contact factory for exact order code con-
sumption
100 000 A RMS symmetrical
10 000 A

2.2.7 OUTPUTS

0.1 A max. (resistive load)
IMPEDANCE
2 W RESISTOR
1 W RESISTOR
20 KΩ
50 KΩ
5 KΩ
2 KΩ
2 KΩ
2 KΩ
2 KΩ
2 KΩ
< 0.6 ms
265 V DC
30 A as per ANSI C37.90
300 A
UL508
Utility
application
(autoreclose
scheme)
5 ops /
5000 ops /
0.2 s-On,
1 s-On, 9 s-Off
0.2 s-Off
within 1
1000 ops /
minute
0.5 s-On, 0.5 s-Off
3.2 A
L/R = 10 ms
1.6 A
10 A
L/R = 20 ms
L/R = 40 ms
0.8 A
L/R = 40 ms
2
Industrial
application
10000 ops /
0.2 s-On,
30 s-Off
10 A
L/R = 40 ms
2-15