5.6 CONTROL ELEMENTS
The
PICKUP DELAY
alarms.
NOTE
EXAMPLE 2: BREAKER TRIP CIRCUIT INTEGRITY MONITORING
If it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method to
maintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the fig-
ure below). This can be achieved by connecting a suitable resistor (see figure below) across the auxiliary contact in the trip
circuit. In this case, it is not required to supervise the monitoring circuit with the breaker position – the
selected to "Off". In this case, the settings will be:
DIGITAL ELEMENT
5
UR Relay - Form-A
I = Current Monitor
V = Voltage Monitor
827074A2.VSD
5-180
setting should be greater than the operating time of the breaker to avoid nuisance
1
DIGITAL ELEMENT
FUNCTION: Enabled
DIG ELEM
MESSAGE
Bkr Trip Cct Out
DIG ELEM
MESSAGE
Cont Op 1 VOff
DIG ELEM
MESSAGE
DELAY:
DIG ELEM
MESSAGE
DELAY:
DIG ELEM
MESSAGE
Off
DIGITAL ELEMENT
MESSAGE
TARGET: Self-reset
DIGITAL ELEMENT
MESSAGE
EVENTS: Enabled
DC+
H1a
I
H1c
V
H1b
52a
R
Trip
Coil
DC–
Figure 5–106: TRIP CIRCUIT EXAMPLE 2
D60 Line Distance Relay
1
1 NAME:
1 INPUT:
1 PICKUP
0.200 s
1 RESET
0.100 s
1 BLOCK:
1
1
Table 5–21: VALUES OF RESISTOR 'R'
POWER
SUPPLY (V DC)
24
30
48
110
By-pass
125
Resistor
250
5 SETTINGS
setting is
BLOCK
RESISTANCE
POWER
(OHMS)
(WATTS)
1000
2
5000
2
10000
2
25000
5
25000
5
50000
5
GE Multilin