GE D60 Instruction Manual page 264

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
SETTING
AR FUNCTION:
Enable=1
Disable=0
D60, L90 Relay Only
FLEXLOGIC OPERAND
LINE PICKUP OP
AND
SETTING
OR
AR BLOCK:
Off = 0
SETTING
AR BKR MAN CLOSE:
Off = 0
OR
BKR MANUAL CLOSE:
(From sheet 3)
SETTING
AR 1P INIT:
Off = 0
OR
FLEXLOGIC OPERAND
TRIP 1-POLE
SETTING
AR 3P INIT:
Off = 0
OR
FLEXLOGIC OPERAND
TRIP AR INIT 3-POLE
5
SETTING
AR 3P TD INIT:
Off = 0
SETTING
BKR ONE POLE OPEN:
Off = 0
OR
BKR ONE POLE OPEN
SETTING
BKR 3 POLE OPEN:
Off = 0
OR
BKR 3 POLE OPEN
RESET
CLOSE BKR1 OR BKR2
FLEXLOGIC OPERAND
AR SHOT COUNT>0
SETTING
AR PAUSE
Off = 0
SHOT COUNT = MAX
SETTING
AR M0DE:
1 Pole
3 Pole - A
3 Pole -B
1 & 3 Pole
D60, L60 Relays Only From Phase Selector
FLEXLOGIC OPERAND
PHASE SELECT MULTI-P
SETTING
AR MULTI-P FAULT:
Off = 0
SETTING
AR RESET:
Off = 0
BKR CLOSED
10s
AND
0
5-174
FLEXLOGIC OPERANDS
AR ENABLED
AR DISABLED
SETTING
AND
AR BLK TIME UPON MAN
CLS :
0
AND
LO
OR
OR
AND
AND
OR
AND
AND
OR
OR
OR
0
5ms
OR
Evolving fault
AR DISABLED
OR
Figure 5–100: SINGLE-POLE AUTORECLOSE LOGIC (Sheet 1 of 3)
D60 Line Distance Relay
FLEXLOGIC OPERAND
S
Latch
AR RIP
R
S
Latch
R
FLEXLOGIC OPERAND
AR 1-P RIP
SETTING
AR 1-P DEAD TIME:
AND
FLEXLOGIC OPERAND
AR 3-P/1 RIP
SETTING
S
AR 3-P DEAD TIME 1:
Latch
OR
R
AND
SHOT COUNT=1
(From Sheet 2)
SHOT
COUNT=2
(From
Sheet 2)
S
OR
AND
Latch
R
OR
AND
SHOT COUNT=3
(From Sheet 2)
BKR FAIL TO RECLS
(from sheet 2)
AND
SETTING
AR INCOMPLETE SEQ.
TIMER:
OR
AND
AND
OR
FLEXLOGIC OPERAND
OR
AR FORCE 3P TRIP
FLEXLOGIC OPERAND
OR
AR ZONE 1 EXTENT
5 SETTINGS
AR INITIATE
(To page 2, Reset AR TRANSFER TIMER)
1.25 cycle
To: AR FORCE 3P TRIP
(Evolving fault)
0
SETTING
AR EXTEND DEAD TIME
1:
AND
Off = 0
0
SETTING
OR
AR DEAD TIME 1
EXTENSION:
OR
0
FLEXLOGIC OPERAND
AR 3-P/2 RIP
0
SETTING
OR
AR 3-P DEAD TIME 2:
AND
0
OR
OR
FLEXLOGIC OPERAND
AR 3-P/3 RIP
SETTING
AR 3-P DEAD TIME 3:
AND
0
FLEXLOGIC OPERAND
AR 3-P/4 RIP
SETTING
AR 3-P DEAD TIME 4:
AND
0
827089AM.CDR
AND
AND
FLEXLOGIC OPERAND
OR
AR LO
0
AND
RESET (to sheet 2)
FLEXLOGIC OPERAND
AR INCOMPLETE SEQ
GE Multilin
CLOSE (to page 2)

Advertisement

Table of Contents
loading

Table of Contents