Relay Activation; Relay Passwords; Flexlogic™ Customization - GE D60 Instruction Manual

Line distance relay
Hide thumbs Also See for D60:
Table of Contents

Advertisement

1.5 USING THE RELAY
1
The relay is defaulted to the "Not Programmed" state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Ser-
vice LED off. The relay in the "Not Programmed" state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the "Programmed" state.
Select the menu message
RELAY SETTINGS:
Not Programmed
To put the relay in the "Programmed" state, press either of the
plate Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually
(refer to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup Help file) via the EnerVista UR
Setup software interface.
It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
operate breakers via faceplate keypad
change state of virtual inputs
clear event records
clear oscillography records
operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
NOTE
FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex-
Logic™ section in Chapter 5 for additional details.
1-12
SETTINGS
PRODUCT SETUP
D60 Line Distance Relay
INSTALLATION
RELAY SETTINGS
VALUE
keys once and then press
1.5.6 FLEXLOGIC™ CUSTOMIZATION
1 GETTING STARTED

1.5.4 RELAY ACTIVATION

. The face-

1.5.5 RELAY PASSWORDS

GE Multilin

Advertisement

Table of Contents
loading