5.2 PRODUCT SETUP
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the D60 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the D60 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode,
set and
SNTP FUNCTION
values are obtained and averaged, it generally takes three to four minutes until the D60 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the D60 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the
D60 then listens to SNTP messages sent to the "all ones" broadcast address for the subnet. The D60 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality.
PATH: SETTINGS
PRODUCT SETUP

MODBUS USER MAP

The Modbus User Map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
5
address in the
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
PATH: SETTINGS
PRODUCT SETUP
REAL TIME
CLOCK
The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same
accuracy as an electronic watch, approximately ±1 minute per month. If an IRIG-B signal is connected to the relay, only the
current year needs to be entered. See the
The
REAL TIME CLOCK EVENTS
5-22
SNTP SERVER IP ADDR
is "Enabled", the D60 attempts to obtain time values from the SNTP/NTP server. Since many time
SNTP SERVER IP ADDR
MODBUS USER MAP
ADDRESS
VALUE:
ADDRESS 256:
MESSAGE
VALUE:
line (this value must be converted from hex to decimal format). The corresponding value is dis-
values can be entered as required in any of the register positions.
ADDRESS

REAL TIME CLOCK

IRIG-B SIGNAL TYPE:
None
REAL TIME CLOCK
MESSAGE
EVENTS: Disabled
COMMANDS
setting allows changes to the date and/or time to be captured in the event record.
D60 Line Distance Relay
must be set to the SNTP/NTP server IP address. Once this address is
setting to "0.0.0.0" and
Range: 0 to 65535 in steps of 1
1:
0
0
Range: 0 to 65535 in steps of 1
0
0
lines automatically returns values for the previous
ADDRESS
Range: None, DC Shift, Amplitude Modulated
Range: Disabled, Enabled
menu to manually set the relay clock.
SET DATE AND TIME
5 SETTINGS
to "Enabled". The
SNTP FUNCTION
5.2.5 MODBUS USER MAP
5.2.6 REAL TIME CLOCK
GE Multilin