Function And Performance Specifications - Omron EJ1 - 07-2008 Operation Manual

Devicenet communications unit for ej1 temperature controllers
Table of Contents

Advertisement

Specifications
Item
Error control
Power supply
Note
1-2-2

Function and Performance Specifications

Item
Maximum number of Temperature
Controllers that can be connected
Applicable Temperature Control-
lers
Power supply
Copying
10
CRC error detection
Power supplied from DeviceNet communications connector (DeviceNet commu-
nications power supply and DeviceNet Communications Unit internal circuit
power supply)
1. When a CS/CJ-series DeviceNet Unit is used as the master, two blocks
can be used for the IN Area (the connections can also be set). When a
CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is used, the
IN Area must be in 1 block, and up to 100 words (200 bytes) are allocated.
(Only polling connections can be used.)
2. When a CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is
used, up to 32 words can be allocated in the master for a single node.
3. The set points, alarm setting values, PID constants, and other Tempera-
ture Controller parameters can be set together.
16
Note Up to 15 Units can be connected side by side. The 16th Unit is connected
using distributed placement by using an End Unit.
(TC4)
• EJ1N-TC4A-QQ
• EJ1N-TC4B-QQ
(TC2)
• EJ1N-TC2A-QNHB
• EJ1N-TC2B-QNHB
• EJ1N-TC2A-CNB
• EJ1N-TC2B-CNB
Power is supplied via the terminal block of the End Unit (power supply for communi-
cations between the DeviceNet Communications Unit and Temperature Controllers
and power supply for internal circuits of the Temperature Controllers).
The parameters of a connected Temperature Controller can be uploaded or down-
loaded as a batch by using the DeviceNet Communications Unit's DIP switch or an
explicit message. The bank, G3ZA, and G3PW parameters are not copied.
The uploaded parameters are stored in the DeviceNet Communications Unit.
Specifications
Specifications
Section 1-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ej1 devicenet communications unit

Table of Contents