Setting Tag Data Links - Omron ERT1 Series Operation Manual

Ethernet/ip slave units
Table of Contents

Advertisement

Overview of System Startup Procedure
1,2,3...
1,2,3...
1,2,3...
2-1-3

Setting Tag Data Links

1,2,3...
1. Set the rotary switches (hexadecimal) on the Slave Unit to the initial IP ad-
dress.
The initial IP address will be 192.168.250.n (where n is the value to which
the rotary switches are set).
(If the rotary switches are set to 0A, the initial IP address will be
192.168.250.10.)
After setting the rotary switches, turn ON the power to the Slave Unit.
2. Check to be sure the initial IP address is correct.
3. Step III: Set the IP address using the Network Configurator.
Refer to Common Procedure 4. Connecting the Network Configurator On-
line and Common Procedure 6-2 Setting IP Addresses Using the Network
Configurator.
4. Set the rotary switches to 00 and then turning the cycle the power supply.
Operation will start with the new IP address.
Setting the IP Address with the BOOTP/DHCP Server
This method involves first using the rotary switches to set an initial IP address,
and then using the Network Configurator and the BOOTP/DHCP server to set
the desired IP addresses.
1. Set the rotary switches to 00.
2. Set the IP address using the BOOTP/DHCP server.
Refer to Common Procedure 6-3. Setting IP Address Using the BOOTP
Server.
Setting the IP Address with the Rotary Switches
1. Set the rotary switches (hexadecimal) on the Slave Unit to the desired IP
address.
The initial IP address will be 192.168.250.n (where n is the value to which
the rotary switches are set).
(If the rotary switches are set to 0A, the initial IP address will be
192.168.250.10.)
After setting the rotary switches, turn ON the power to the Slave Unit.
Set data links using the OMRON Network Configurator.
Connecting to the Network
Refer to Common Procedure 4. Connecting the Network Online.
Uploading the Network Configuration
Refer to Common Procedure 5. Uploading the Current Network Configuration.
Setting Tag Data Links
Set the tag data links.
1. Refer to Common Procedure 7-2. Registering a Tag Set with the PLC.
Create a 2-byte output tag.
2. Set a connection.
The subsequent steps are performed using the CJ2B-EIP21 Edit Device
Parameters Dialog Box.
Section 2-1
9