Error Log Clear; Udp Open Request - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference
Response Codes

11-3-8 ERROR LOG CLEAR

Command Block
Response Block
Response Codes

11-3-9 UDP OPEN REQUEST

Command Block
Response Block
Results Storage
Format
Parameters
UDP Socket Number
(Command)
Results Storage Area
(Command)
Local UDP Port Number
(Command)
Response code
0000
Normal
1001
Command too large
1002
Command too small
1103
Beginning record number is out of range
110C
The number of read records is 0.
Clears the number of records stored in the Ethernet Unit error log.
21
03
Command
code
21
03
Command
Response
code
code
Response code
0000
Normal
1001
Command too large
Requests processing to open a socket.
27
01
Command
UDP
Results storage area
code
socket
number
27
01
Command
Response
code
code
Results storage
response code
The UDP socket number to be opened specified as 2 bytes between 1 and 8.
The area in which the results of the command execution are stored. The first
byte specifies the memory area and data type (variable type). The 2nd to 4th
bytes specify the beginning address of the results storage area. Refer to
page 216 for details about the variable types and addresses that can be spec-
ified.
The UDP port number for communications with the socket is specified as 2
bytes (0 cannot be specified). Packets received at this port are distributed to
Section 11-3
Description
Description
Local UDP
port number
223

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07

Table of Contents