Udp Close Request - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Command/Response Reference
Results Storage Area Response Codes

11-3-12 UDP CLOSE REQUEST

Command Block
Response Block
Results Storage
Format
Parameters
UDP Socket Number
(Command)
Results Storage Area
(Command)
Response Codes
Response code
0000
Normal
003E
Internal buffer cannot be reserved due to high reception load
(ENOBUFS).
0042
The send destination IP address is a broadcast address and
the number of bytes sent exceeds 1,472. (EMSGSIZE)
004C
Incorrect network number.
Incorrect destination IP address (EADDRNOTAVAIL).
004E
Incorrect destination IP address (ENETUNREACH).
No network number in IP router table.
Router incorrectly set.
0051
Router incorrectly specified.
Incorrect destination IP address (EHOSTUNREACH).
Requests processing to close a socket.
27
04
Command
UDP
code
socket
number
27
04
Command
Response
code
code
Response
code
The UDP socket number to be closed specified as 2 bytes between 1 and 8.
The area in which the results of the command execution are stored. The first
byte specifies the memory area and data type (variable type). The 2nd to 4th
bytes specify the beginning address of the results storage area. Refer to
page 216 for details about the variable types and addresses that can be spec-
ified.
Response code
0000
Normal
0105
Local IP address setting error
0302
CPU Unit error; execution not possible.
1001
Command too large
1002
Command too small
1100
UDP socket number is out of range.
1101
The variable type for the results storage area is out of range.
1103
Non-zero bit address specified for the results storage area.
Description
Results storage area
Description
Section 11-3
227

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07

Table of Contents