Omron CJ1W-ETN11 Operation Manual page 210

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Internode Test
Starting and Stopping the Internode Test
9-3-2
Checking Results
Test Status
15
14
Bit
+3
Error code
Error Code
Bit 01 of the first word in the words allocated to the Ethernet Unit in the CPU
Bus Unit Area is used as the Internode Test Start Switch. Turn ON bit 01 to
start the internode test and turn bit 01 OFF to stop the internode test. The
address of the word containing the Internode Test Start Switch is calculated
by the following formula:
Word = 1500 + (25 x unit number)
15
14
Bit
The internode test run status can be confirmed using the TS indicator on the
Unit's front panel or the Internode Test Flag (error status, bit 8) in the allocated
words in the CIO Area.
Error status area (1 word) = CIO 1500 + (25 × unit number) + 18
TS indicator
Lit
Not lit
The results of the internode test are stored in the fourth through ninth words of
the portion of the CPU Bus Unit Area allocated to the Ethernet Unit. The sta-
tus information area stores the test status and numbers of test runs and
errors.
The result of the test run and descriptions of errors are stored as the test sta-
tus. The test status is stored at the word whose address is calculated by the
following formula:
Word = D03000 + (100 x unit number) + 3
13
12
11
10
9
8
0
0
0
0
If the test is run repeatedly, the code for the latest test results is stored.
Bit
15
14
0
0
0
0
0
1
0
1
13
12
11
10
9
8
Internode Test Flag
(error status, bit 8)
1
0
7
6
5
4
3
0
0
0
Error flags
1: Routing table error
1: Send parameter error
13
0
Normal
1
Timeout error
0
Response (response code) error
1
Send error
Section 9-3
7
6
5
4
3
Internode Test Start Switch
0: Stop internode test
1: Start internode test
Run status
Internode test running
Internode test stopped
2
1
0
1: Timeout error
1: Response error
1: Send error
1: Data not matched
Description
2
1
0
189

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07

Table of Contents