DM Area Allocations

4-4

DM Area Allocations

Offset
Bit
15
m
Internode test remote network address and node number
m+1
Internode test number of send bytes
m+2
Internode test response monitoring time
m+3
Internode test status
m+4
Number of internode test runs
m+5
Number of internode test timeout errors
m+6
Number of internode test response errors
m+7
Number of internode test send errors
m+8
Number of times internode test data did not match
m+9
TCP socket No. 1 connection status
m+16
TCP socket No. 8 connection status
m+17
Mail status
m+18
Socket Services Parameter Area 1
m+28
Socket Services Parameter Area 2
m+88
Socket Services Parameter Area 8
m+98
IP Address Display/Setting Area (See note.)
m+99
Internode Test Remote Network Address and Node Number (CPU Unit to Ethernet Unit)
Internode Test Number of Send Bytes (CPU Unit to Ethernet Unit)
The various kinds of data are stored in the offset positions shown in the fol-
lowing diagram, from the beginning word in the area for each Unit.
The beginning word m is calculated by the following equation:
Beginning word m = D30000 + (100 x unit number)
8
7
Note For CS-series Ethernet Units, this area is the IP Address Display Area and
data in this area can be transferred from the Ethernet Unit to the CPU Unit
only. For CJ-series Ethernet Units, this area is the IP Address Display/Setting
Area and data in this area can be transferred in either direction.
The meanings of the items shown in the above diagram are explained on the
following pages. For details regarding the related communications services
shown in the diagram, refer to the indicated sections.
15 14 13 12 11 10 9
m
Remote network address
Specify the remote network address and node number in hexadecimal within
the following ranges:
Remote network address: 00 to 7F Hex (0 to 127 decimal)
Remote node number: 01 to 7E Hex (0 to 126 decimal)
If a remote network address is set to 00, it will specify the local network (i.e.,
the network to which the Ethernet Unit is connected.)
15 14 13 12 11 10 9
m+1
0
Data direction
CPU Unit to Ethernet Unit
Ethernet Unit to CPU Unit
CPU Unit to Ethernet Unit
Ethernet Unit to CPU Unit or
CPU Unit to Ethernet Unit
8
7
8
Number of send bytes (0000 to 07CC Hex)
Section 4-4
Related communications services
Internode Test Function
(Refer to 9-3 Internode Test.)
Socket Services
(Refer to Section 6
Socket Services.)
Mail function
(Refer to Section 8 Mail.)
Socket Services
(Refer to Section 6
Socket Services.)
6
5
4
3
2
1
Remote node number
7
6
5
4
3
2
1
0
0
73