Troubleshooting with Response Codes
Main code
Sub-
code
02: Remote node
01
error
02
05
03: Communica-
01
tions controller
error
02
04
04: Not execut-
01
able
(Service not sup-
ported.)
05: Routing error
01
02
03
04
10: Command for-
01
mat error
02
03
05
208
Probable cause
IP address of remote node not set cor-
rectly in IP address table or IP router table.
No node with the specified unit address.
Message packet was corrupted by trans-
mission error.
Response time-out, response watchdog
timer interval too short.
The transmission frame may be corrupted
or the internal reception buffer full.
Error occurred in the communications con-
troller, ERC indicator is lit.
CPU Unit error occurred in the PC at the
remote node.
Unit number setting error
An undefined command has been used.
A short frame (4 bytes) is being used for
the FINS header frame.
Remote node is not set in the routing
tables.
Routing tables aren't registered com-
pletely.
Routing table error
The maximum number of relay nodes (2)
was exceeded in the command.
The command is longer than the max. per-
missible length.
The command is shorter than min. permis-
sible length.
The designated number of data items dif-
fers from the actual number in the com-
mand data.
Data for another node on the same net-
work was received from the network.
An attempt was made to send response
data for a broadcast address.
Remedy
Set IP address of remote node into IP address
table and, if internetwork transmission is
required, into the IP router table.
Check the remote node's unit address and
make sure the correct one is being used in the
control data.
Check the protocol and controller status by
reading them with FINS commands. Increase
the number of transmit retry attempts.
Increase the value for the response monitor
time in the control data.
Read out the error log and correct as required.
Take corrective action, referring to troubleshoot-
ing procedures in this section.
Check CPU Unit indicators at the remote node
and clear the error in the CPU Unit (refer to the
PC's operation manuals)
Make sure the unit number is within the speci-
fied range and that the same unit number is not
used twice in the same network.
Check the command code and be sure the
command is supported by the Unit to which you
are sending it.
Check the FINS header frame length. The
Ethernet Unit does not support short headers.
Set the destination address in the routing
tables.
Set routing tables at the local node, remote
node, and any relay nodes.
Set the routing tables correctly.
Redesign the network or reconsider the routing
table to reduce the number of relay nodes in the
command. Communications are possible on
three network levels, including the local net-
work.
Check the command format of the command
and set it correctly. Be sure broadcast transmis-
sions don't exceed 1,473 bytes.
Check the command format of the command
and set it correctly.
Check the number of items and the data, and
make sure that they agree.
Check the header parameters in the command
data and be sure the correct command format
is being used.
Section 10-6