Sending Commands From a PC
Usage
Command
MR
I/O memory area
01
access
01
01
01
01
Parameter area
02
access
02
02
Program area
03
access
03
03
Operating mode
04
changes
04
Machine configura-
05
tion reading
05
Status reading
06
06
Time data access
07
07
Message display
09
Access rights
0C
0C
0C
Error log
21
21
21
Commands Addressed to CS/CJ-series CPU Units
The following table provides a list of FINS commands that can be processed
by a CS/CJ-series CPU Unit. For details, refer to the CS/CJ-series Program-
mable Controllers Communications Commands Reference Manual (W342).
For details on FINS commands that can be processed by the Ethernet Unit,
refer to Section 11 FINS Commands Addressed to Ethernet Units.
code
SR
01
MEMORY AREA READ
02
MEMORY AREA WRITE
03
MEMORY AREA FILL
04
MULTIPLE MEMORY AREA READ
05
MEMORY AREA TRANSFER
01
PARAMETER AREA READ
02
PARAMETER AREA WRITE
03
PARAMETER AREA FILL (CLEAR)
06
PROGRAM AREA READ
07
PROGRAM AREA WRITE
08
PROGRAM AREA CLEAR
01
RUN
02
STOP
01
CPU UNIT DATA READ
02
CONNECTION DATA READ
01
CPU UNIT STATUS READ
20
CYCLE TIME READ
01
CLOCK READ
02
CLOCK WRITE
20
MESSAGE READ/CLEAR
01
ACCESS RIGHT ACQUIRE
02
ACCESS RIGHT FORCED ACQUIRE
03
ACCESS RIGHT RELEASE
01
ERROR CLEAR
02
ERROR LOG READ
03
ERROR LOG POINTER CLEAR
Name
Reads the contents of consecutive I/O
memory area words.
Writes the contents of consecutive I/O
memory area words.
Writes the same data to the specified
range of I/O memory area words.
Reads the contents of specified non-
consecutive I/O memory area words.
Copies the contents of consecutive I/O
memory area words to another I/O
memory area.
Reads the contents of consecutive
parameter area words.
Writes the contents of consecutive
parameter area words.
Writes the same data to the specified
range of parameter area words.
Reads the UM (User Memory) area.
Writes to the UM (User Memory) area.
Clears the UM (User Memory) area.
Changes the CPU Unit's operating
mode to RUN or MONITOR.
Changes the CPU Unit's operating
mode to PROGRAM.
Reads CPU Unit data.
Reads the model numbers of the device
corresponding to addresses.
Reads the status of the CPU Unit.
Reads the maximum, minimum, and
average cycle time.
Reads the present year, month, date,
minute, second, and day of the week.
Changes the present year, month, date,
minute, second, or day of the week.
Reads and clears messages, and reads
FAL/FALS messages.
Acquires the access right as long as no
other device holds it.
Acquires the access right even if
another device already holds it.
Releases the access right that has been
acquired.
Clears errors or error messages.
Reads the error log.
Clears the error log pointer.