Error Log Clear - Omron CS Series Operation Manual

Ethernet units construction of networks
Hide thumbs Also See for CS Series:
Table of Contents

Advertisement

Command/Response Reference
Error Log Data
(Response)
Precautions
Response Codes
7-3-8

ERROR LOG CLEAR

Command Block
Response Block
Response Codes
168
The specified number of error log records from the beginning record number
is returned sequentially. The total number of bytes in the error log is calculated
as the number of records x 10 bytes/record. Each error log record thus com-
prises 10 bytes, configured as follows:
1st byte
Error code
Error Code, Detailed Information
Details of the error stored in the record. Refer to 8-3-1 Error Log Error Codes
for details.
Minute, Second, Day, Hour, Year, Month
Indicate the time at which the error stored in the record occurred.
If the error log contains fewer records than the number specified in the num-
ber of records parameter, all records stored in the error log at the time the
command is executed will be returned and the command executed will end
normally.
Response code
0000
Normal
1001
Command too large
1002
Command too small
1103
Beginning record number is out of range
110C
The number of read records is 0.
Clears the number of records stored in the Ethernet Unit error log.
21 03
Command code
21 03
Command
Response
code
code
Response code
0000
Normal
1001
Command too large
Detailed
Day Hour Year Month
Minutes Second
information
Description
Description
Section 7-3
10th byte