Advertisement

Installation Guide

5.8 Alarm

Many applications in the ECL Comfort 210 and 310 series have an
alarm function. The alarm function typically activates relay 4 (ECL
Comfort 210) or relay 6 (ECL Comfort 310).
The alarm relay can activate a lamp, a horn, an input to an alarm
transmitting device etc.
The relay in question is activated as long as the alarm condition
is present.
Typical alarms:
Actual flow temperature differs from the desired flow
temperature.
Too low or too high pressure (A376.9)
Extra alarms, for example circulation pump malfunction
(A376.9)
Besides the mentioned alarm types, alarm can be activated when a
temperature sensor becomes defective (i.e. outside the measuring
range -60 ... 150 °C). This is the case if the connection to the
temperature sensor is disconnected, short-circuited or the sensor
itself is defective.
See the set-up procedure for temperature sensor alarms in section
'Common controller settings' , 'System' , ' Raw input overview' .
5.8.1 Temp. monitor.
Upper difference
Circuit
1
The alarm is activated if the actual flow temperature increases more than
the set difference (acceptable temperature difference above the desired
flow temperature). See also 'Delay'.
OFF:
The alarm function is not active.
1 ... 30 K: The alarm function is active if the actual temperature
gets above the acceptable difference.
Lower difference
Circuit
1
The alarm is activated if the actual flow temperature decreases more than
the set difference (acceptable temperature difference below the desired
flow temperature). See also 'Delay'.
OFF:
The alarm function is not active.
1 ... 30 K: The alarm function is active if the actual temperature
gets below the acceptable difference.
Danfoss District Energy
ECL Comfort 310, application A376
11147
Setting range
Factory setting
OFF / 1 ... 30 K
OFF
11148
Setting range
Factory setting
OFF / 1 ... 30 K
OFF
Flow temp. °C
Flow temp. °C
VI.GU.B1.02
Upper difference (set
value)
Desired flow temp.
Outdoor temp.
Lower difference (set
value)
Desired flow temp.
Outdoor temp.
DEN-SMT/DK