Danfoss ECL Comfort 310 Installation Manual page 126

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide
Max. flow T— A376.9
Circuit
2
The alarm is activated when the flow temperature exceeds the set value.
Delay — A376.9
Circuit
2
The alarm is activated when the flow temperature has been above the limit
set in 'Max. flow T' for a longer time (in seconds) than the set value.
126
DEN-SMT/DK
ECL Comfort 310, application A376
12079
Factory setting
Setting range
10 ... 110 °C
90 °C
12180
Setting range
Factory setting
5 ... 250 s
60 s
VI.GU.B1.02
Danfoss District Energy

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents