Installation Guide
A376.2, example b
Indirectly connected heating and DHW system with flow switch (typically district heating). Heating circuit 2 is connected as a sub-circuit
of heating circuit 1. Alternatively, heating circuit 2 can be a floor heating circuit.
S 7
Special settings for type A376.2, example b:
Navigation:
Circuit 1 must be able to receive a heat demand from circuit 2:
MENU \ Settings \ Application: 'Demand offset'
Circuit 2 must be able to send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
Circuit 3 should not send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
* This value is added to the heat demand value from circuit 2.
Danfoss District Energy
ECL Comfort 310, application A376
S
1
S 3
M2
S 5
S 4
M1
S 6
S 8
ECL 310
R6
P
2
M3
S 9
P
3
S10
P 1
ID no.:
11017
12500
13500
VI.GU.B1.02
(S2)
(S2)
Recommended setting:
3 K*
ON
OFF
DEN-SMT/DK