Adapt. time (adaptation time)
Circuit
3
Controls how fast the return temperature adapts to the desired return
temperature limit (I control).
OFF:
The control function is not influenced by the 'Adapt.
time' .
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
Priority (priority for return temp. limitation)
Circuit
3
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
Danfoss District Energy
ECL Comfort 310, application A376
13037
Setting range
Factory setting
25 s
OFF / 1 ... 50 s
13085
Setting range
Factory setting
OFF / ON
OFF
The adaptation function can correct the desired flow temperature
with max. 8 K.
The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)'.
The influence factors are set in heating circuit 1.
If the return temperature limitation value in heating circuit 1 is higher
than the return temperature limitation value in the DHW circuit, the
highest value is used.