Danfoss ECL Comfort 310 Installation Manual page 17

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide
A376.9, example b
Indirectly connected heating and DHW system with pressure transmitters and alarm input (typically district heating). Heating circuit 2 is
connected as a sub-circuit of heating circuit 1. Alternatively, heating circuit 2 can be a floor heating circuit:
S
S12
Special settings for type A376.9, example b:
Navigation:
Circuit 1 must be able to receive a heat demand from circuit 2:
MENU \ Settings \ Application: 'Demand offset'
Circuit 2 must be able to send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
Circuit 3 should not send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
* This value is added to the heat demand value from circuit 2.