Danfoss ECL Comfort 310 Installation Manual page 26

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide
A376.9:
Description
Terminal
19
Relay output, schedule in 'Common controller settings' ,
18
R6
17
R5
Not to be used
16
Alarm
15
14
Phase for circulation pumps
13
P3
Heating circulation pump, ON / OFF, circuit 2
12
P2
Heating circulation pump, ON / OFF, circuit 1
11
P1
DHW circulation pump, ON / OFF, circuit 3
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
M1
Phase for motorized control valve output, circuit 3
7
M1
Motorized control valve - opening
6
M1
Motorized control valve - closing
5
M2
Phase for motorized control valve output, circuit 1 and circuit 2
4
M2
Motorized control valve - opening
3
M2
Motorized control valve - closing
2
M3
Motorized control valve - opening
1
M3
Motorized control valve - closing
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
26
DEN-SMT/DK
ECL Comfort 310, application A376
For connection of the 0–10 V controlled motorized control valves, see
Electrical connections, 24 V a.c. for ECA 32, application A376.3.
VI.GU.B1.02
Max. load
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
Danfoss District Energy