Water Meter - Danfoss ECL Comfort 310 Installation Manual

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide

7.7 Water meter

CW consump. — A376.9
Circuit
3
The displayed value (actual value) is based on pulses from the cold water
meter and 'Pulse value' (13513).
Pulse value — A376.9
Circuit
3
Setting the value of each pulse from the cold water meter.
The value is used to express the actual cold water consumption.
0.1:
Each pulse from the cold water meter expresses a
consumption of 0.1 liter.
1000.0: Each pulse from the cold water meter expresses a
consumption of 1000.0 liter.
Preset — A376.9
Circuit
3
Is used for resetting the measured water consumption (registered by the
cold water meter).
Via the Modbus communication a value can be preset to a defined value, for
example if the water meter is replaced.
OFF:
Normal status.
ON:
Activation of the reset / preset.
Danfoss District Energy
ECL Comfort 310, application A376
Setting range
Factory setting
Read-out only
13513
Setting range
Factory setting
0.1 ... 1000.0 l
10.0 l
13514
Setting range
Factory setting
OFF / ON
OFF
VI.GU.B1.02
DEN-SMT/DK
143