2.5.5 Electrical connections, Pt 1000 temperature sensors and signals
A376:
Terminal
Sensor / description
29 and 30 S1
Outdoor temperature
sensor*
28 and 30 S2
Room temperature
sensor***, heating circuit 1
(A376.1 / A376.3)
Room temperature
sensor***, heating circuit 1 /
2 (A376.2)
Return temperature sensor,
monitoring only, circuit 1
(A376.9)
27 and 30 S3
Flow temperature sensor,
heating circuit 1**
26 and 30 S4
Flow temperature sensor,
DHW circuit 3**
25 and 30 S5
Return temperature sensor,
heating circuit 1
24 and 30 S6
Return temperature sensor,
DHW circuit 3
23 and 30 S7
Room temperature
sensor***: heating circuit 2
(A376.1 / A376.3)
Supply flow temperature
sensor (A376.2)
0–10 V pressure transmitter
signal (A376.9)
22 and 30 S8
Flow switch, only in A376.2
Alarm input, only in A376.9
21 and 30 S9
Flow temperature sensor**,
heating circuit 2
20 and 30 S10
Return temperature sensor,
heating circuit 2
Return temperature sensor,
monitoring only, circuit 2
(A376.9)
*
If the outdoor temperature sensor is not connected or the
cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C. The outdoor temperature
sensor is common for both heating circuits.
**
The flow temperature sensor must always be connected
in order to have the desired functionality. If the sensor is
not connected or the cable is short-circuited, the motorized
control valve closes (safety function).
*** Only for room temperature sensor connection. The room
temperature signal can alternatively be available from a
Remote Control Unit (ECA 30 / 31). See 'Electrical connections,
ECA 30 / 31'.
Factory established jumper:
30 to common terminal.
36
DEN-SMT/DK
ECL Comfort 310, application A376
Type
(recomm.)
ESMT
ESM-10
ESM-10
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-10
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
VI.GU.B1.02