Installation Guide
Alarm high — A376.9
Circuit
1
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is above the set limit.
Alarm low — A376.9
Circuit
1
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is below the set limit.
Alarm time-out — A376.9
Circuit
1
The pressure alarm is activated when the measured signal has been above
or below the limits for a longer time (in seconds) than the set value.
Digital S8 — A376.9
Circuit
1
Access to settings related to alarm input S8.
Alarm value — A376.9
Circuit
1
The alarm is based on a digital input applied to S8.
0:
The alarm function is active when a switch is closed.
1:
The alarm function is active when a switch is open.
Alarm time-out — A376.9
Circuit
1
The alarm is activated when the switch has been closed or opened for a
longer time (in seconds) than the set value.
Max. temp. — A376.9
Circuit
1
Access to settings related to max. flow temperature alarm.

Danfoss District Energy

ECL Comfort 310, application A376
11614
Setting range
Factory setting
0.0 ... 6.0
2.3
11615
Factory setting
Setting range
0.0 ... 6.0
0.0
11617
Setting range
Factory setting
0 ... 240 s
30 s
Factory setting
Setting range
11636
Setting range
Factory setting
0 / 1
11637
Setting range
Factory setting
0 ... 240 s
30 s
Setting range
Factory setting
0