Application - Danfoss ECL Comfort 310 Installation Manual

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide

5.7 Application

ECA addr. (choice of Remote Control Unit)
Circuit
1
Decides the communication with the Remote Control Unit.
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
Demand offset
Circuit
1
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
1 ... 20: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
P demand
Circuit
1
Choose conditions for the circulation pump in the heating circuit.
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T'.
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T'.
Danfoss District Energy
ECL Comfort 310, application A376
11010
Factory setting
Setting range
OFF / A / B
OFF
11017
Setting range
Factory setting
OFF / 1 ... 20 K
OFF
11050
Factory setting
Setting range
OFF / ON
OFF
The Remote Control Unit has no influence on the DHW control.
The Remote Control Unit must be set accordingly (A or B).
Temp.
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
The circulation pump is always controlled according to frost protection
conditions.
VI.GU.B1.02
Setting in
'Demand offset'
Des. flow temp.,
circuit 1
Des. flow temp.,
circuit 2
Time
DEN-SMT/DK
93