Settings Overview - Danfoss ECL Comfort 310 Installation Manual

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide

4.0 Settings overview

It is recommendable to make a note of any changed settings in the empty columns.
Setting
Heat curve
Temp. max. (flow temp. limit, max.)
Temp. min. (flow temp. limit, min.)
Infl. - max. (room temp. limitation, max.)
Infl. - min. (room temp. limitation, min.)
Adapt. time (adaption time)
High T out X1 (return temp. limitation, high limit, X-axis)
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Low T out X2 (return temp. limitation, low limit, X-axis)
High limit Y2 (return temp. limitation, high limit, Y-axis)
Infl. - max. (return temp. limitation - max. influence)
Infl. - max. (return temp. limitation - max. influence) — A376.9
Infl. - min. (return temp. limitation - min. influence)
Adapt. time (adaptation time)
Priority (priority for return temp. limitation)
Actual (actual flow or power)
Actual limit (limitation value)
High T out X1 (flow / power limitation, high limit, X-axis)
Low limit Y1 (flow / power limitation, low limit, Y-axis)
Low T out X2 (flow / power limitation, low limit, X-axis)
High limit Y2 (flow / power limitation, high limit, Y-axis)
Adapt. time (adaptation time)
Filter constant
Input type
Units
Auto saving (saving temp. dependent on outdoor temp.)
Boost
Ramp (reference ramping)
Optimizer (optimizing time constant)
Pre-stop (optimized stop time)
Based on (optimization based on room / outdoor temp.)
Total stop
Cut-out (limit for heating cut-out)
Parallel operation
Motor pr. (motor protection)
Xp (proportional band)
Xp (proportional band) — A376.9
Tn (integration time constant)
Tn (integration time constant) — A376.9
M run (running time of the motorized control valve)
M run (running time of the motorized control valve) — A376.9
70
DEN-SMT/DK
ECL Comfort 310, application A376
ID
11178
11177
11182
11183
11015
11031
11032
11033
11034
11035
11035
11036
11037
11085
11110
11111
11119
11117
11118
11116
11112
11113
11109
11115
11011
11012
11013
11014
11026
11020
11021
11179
11043
11174
11184
11184
11185
11185
11186
11186
Page
Factory settings in circuit(s)
1
2
75
1.0
76
90 °C
76
10 °C
77
-4.0
78
0.0
78
OFF
79
15 °C
79
40 °C
79
-15 °C
80
60 °C
80
-2.0
80
0.0
80
0.0
81
25 s
81
OFF
82
82
82
15 °C
999.9
83
l/h
83
-15 °C
999.9
83
l/h
83
OFF
83
10
84
OFF
84
l/h
85
-15 °C
85
OFF
86
OFF
86
OFF
87
ON
87
OUT
87
OFF
88
20 °C
88
OFF
89
OFF
89
80 K
89
85 K
89
30 s
89
25 s
90
30 s
90
120 s