M run (running time of the motorized control valve) —
A376.9
Circuit
3
'M run' is the time in seconds it takes the controlled component
to move from fully closed to fully open position. Set the 'M run'
according to the examples or measure the running time by means
of a stop watch.
M run (running time of the motorized control valve) —
A376.9
Circuit
3
'M run' is the time in seconds it takes the controlled component
to move from fully closed to fully open position. Set the 'M run'
according to the examples or measure the running time by means
of a stop watch.
Nz (neutral zone)
Circuit
3
Set the acceptable flow temperature deviation.
Set the neutral zone to a high value if you can accept a high
variation in flow temperature. When the actual flow temperature
is within the neutral zone, the controller does not activate the
motorized control valve.
Nz (neutral zone) — A376.9
Circuit
3
Set the acceptable flow temperature deviation.
Set the neutral zone to a high value if you can accept a high
variation in flow temperature. When the actual flow temperature
is within the neutral zone, the controller does not activate the
motorized control valve.
134
DEN-SMT/DK
ECL Comfort 310, application A376
13186
Setting range
Factory setting
5 ... 250 s
15 s
13186
Setting range
Factory setting
5 ... 250 s
15 s
13187
Setting range
Factory setting
1 ... 9 K
3 K
13187
Setting range
Factory setting
1 ... 9 K
2 K
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using
the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example:
5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example:
90 degr. x 2 sec. / degr. = 180 sec.
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using
the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example:
5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example:
90 degr. x 2 sec. / degr. = 180 sec.
The neutral zone is symmetrical around the desired flow temperature
value, i.e. half the value is above and half the value is below this
temperature.
The neutral zone is symmetrical around the desired flow temperature
value, i.e. half the value is above and half the value is below this
temperature.
VI.GU.B1.02