Anti-Bacteria - Danfoss ECL Comfort 310 Installation Manual

Application a376
Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide

7.6 Anti-bacteria

On selected days during the week the DHW temperature can
be increased in order to neutralize bacteria in the DHW system.
The desired DHW temperature 'Desired T' (typically 80 °C) will be
present for the selected day(s) and duration.
The anti-bacteria function is not active in frost protection mode.
Day
Circuit
3
Select (mark) the day(s) of the week where the anti-bacteria function must
be active.
M = Monday
= Tuesday
T
W = Wednesday
= Thursday
T
= Friday
F
= Saturday
S
= Sunday
S
Danfoss District Energy
ECL Comfort 310, application A376
Setting range
Factory setting
Weekdays
Desired temp.
80
55
Day / start time
During the anti-bacteria process, the return temperature limitation is
not active.
VI.GU.B1.02
Time
Duration